APPENDIX B — CONTROL MODES WITH
Humidi−MiZer SYSTEM AND ECONOMIZER
Thermostat input shown for cooling demand (versus temperature sensor and set point). Humidistat input shown for dehumidification demand (versus relative humidity sensor and set point). Economizer cooling availability is dependent on outdoor temperature or enthalpy.
Circuit Subcooling mode = REHEAT 1
Circuit HGRH mode = hot gas reheat = REHEAT 2 Circuit ON mode = normal cooling
Thermostat Control type configuration = 0 = Adaptive, or Unit Control Type configuration = 3 = Space Temperature, for
48/50PG and PM
SINGLE-CIRCUIT UNITS
(Thermostat Control Type configuration is ignored)
ECONO AVAILABLE? | Y1 | Y2 | HUMIDISTAT | CIRCUIT A | ECONOMIZER |
|
NO | OFF | OFF | LOW | OFF | Min. Position | (Econo closed if fan off) |
NO | OFF | OFF | HIGH | HGRH | Min. Position |
|
NO | ON | OFF | HIGH | Subcooling | Min. Position |
|
NO | OFF | ON | HIGH | Subcooling | Min. Position | alarm T411: Y2 without Y1 |
NO | ON | ON | HIGH | Subcooling | Min. Position | no alarm |
NO | ON | OFF | LOW | ON | Min. Position |
|
NO | OFF | ON | LOW | ON | Min. Position | alarm T411: Y2 without Y1 |
NO | ON | ON | LOW | ON | Min. Position | no alarm |
YES | OFF | OFF | LOW | OFF | Min. Position | (Econo closed if fan off) |
YES | OFF | OFF | HIGH | HGRH | Min. Position |
|
YES | ON | OFF | HIGH | Subcooling | Min. Position |
|
YES | OFF | ON | HIGH | Subcooling | Min. Position | alarm T411: Y2 without Y1 |
YES | ON | ON | HIGH | Subcooling | Min. Position | no alarm |
YES | ON | OFF | LOW | OFF or ON | Cooling |
|
YES | OFF | ON | LOW | OFF or ON | Cooling | alarm T411: Y2 without Y1 |
YES | ON | ON | LOW | OFF or ON | Cooling | no alarm |
DUAL CIRCUIT UNITS
1-Stage Y1 (Thermostat Control Type configuration = 1)
and
ECONO AVAILABLE? | Y1 | Y2 | HUMIDISTAT | CIRCUIT A | CIRCUIT B | ECONOMIZER |
|
NO | OFF | OFF | LOW | OFF | OFF | Min. Position | (Econo closed if fan off) |
NO | OFF | OFF | HIGH | HGRH | HGRH | Min. Position |
|
NO | ON | OFF | HIGH | Subcooling | HGRH | Min. Position |
|
NO | OFF | ON | HIGH | Subcooling | Subcooling | Min. Position | alarm T411: Y2 without Y1 |
NO | ON | ON | HIGH | Subcooling | Subcooling | Min. Position |
|
NO | ON | OFF | LOW | ON | OFF | Min. Position |
|
NO | OFF | ON | LOW | ON | ON | Min. Position | alarm T411: Y2 without Y1 |
NO | ON | ON | LOW | ON | ON | Min. Position |
|
YES | OFF | OFF | LOW | OFF | OFF | Min. Position | (Econo closed if fan off) |
YES | OFF | OFF | HIGH | HGRH | HGRH | Min. Position |
|
YES | ON | OFF | HIGH | Subcooling | HGRH | Min. Position |
|
YES | OFF | ON | HIGH | Subcooling | Subcooling | Min. Position | alarm T411: Y2 without Y1 |
YES | ON | ON | HIGH | Subcooling | Subcooling | Min. Position |
|
YES | ON | OFF | LOW | OFF or ON | OFF | Cooling |
|
YES | OFF | ON | LOW | OFF or ON | OFF or ON | Cooling | alarm T411: Y2 without Y1 |
YES | ON | ON | LOW | OFF or ON | OFF or ON | Cooling |
|
DUAL-CIRCUIT UNITS
Digital (Thermostat Control Type configuration = 3)
ECONO AVAILABLE? | Y1 | Y2 | HUMIDISTAT | CIRCUIT A | CIRCUIT B | ECONOMIZER |
|
NO | OFF | OFF | LOW | OFF | OFF | Min. Position | (Econo closed if fan off) |
NO | OFF | OFF | HIGH | HGRH | OFF | Min. Position |
|
NO | ON | OFF | HIGH | HGRH | HGRH | Min. Position |
|
NO | OFF | ON | HIGH | Subcooling | HGRH | Min. Position |
|
NO | ON | ON | HIGH | Subcooling | Subcooling | Min. Position |
|
NO | ON | OFF | LOW | ON | OFF | Min. Position |
|
NO | OFF | ON | LOW | ON | ON | Min. Position |
|
NO | ON | ON | LOW | ON | ON | Min. Position |
|
YES | OFF | OFF | LOW | OFF | OFF | Min. Position | (Econo closed if fan off) |
YES | OFF | OFF | HIGH | HGRH | OFF | Min. Position |
|
YES | ON | OFF | HIGH | HGRH | HGRH | Min. Position |
|
YES | OFF | ON | HIGH | Subcooling | HGRH | Min. Position |
|
YES | ON | ON | HIGH | Subcooling | Subcooling | Min. Position |
|
YES | ON | OFF | LOW | OFF or ON | OFF | Cooling |
|
YES | OFF | ON | LOW | OFF or ON | OFF or ON | Cooling |
|
YES | ON | ON | LOW | OFF or ON | OFF or ON | Cooling |
|
112