Carrier 48/50PG C03-14, 48/50PM C16-28 Fan Performance — 48PGF05 Horizontal Units, 48/50PG and PM

Models: 48/50PM C16-28 48/50PG C03-14

1 188
Download 188 pages 11.12 Kb
Page 130
Image 130
Fan Performance — 48PGF05 Horizontal Units

AIRFLOW

 

0.2

(Cfm)

 

Rpm

Bhp

 

1200

456

0.13

1300

477

0.16

1400

500

0.18

1500

524

0.22

1600

550

0.26

1700

576

0.30

1800

604

0.35

1900

633

0.41

2000

662

0.47

AIRFLOW

 

 

Fan Performance — 48PGF05 Horizontal Units

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

0.4

 

0.6

 

0.8

 

 

1.0

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

574

0.20

675

0.28

766

0.37

850

0.46

591

0.23

688

0.32

776

0.41

857

0.50

610

0.27

703

0.36

788

0.45

867

0.55

630

0.31

720

0.40

802

0.50

879

0.60

652

0.35

739

0.45

819

0.55

893

0.66

675

0.40

759

0.50

836

0.61

908

0.72

699

0.46

781

0.57

856

0.68

925

0.79

724

0.52

804

0.63

876

0.75

944

0.87

750

0.59

828

0.71

898

0.83

964

0.95

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

48/50PG and PM

(Cfm)

 

1.2

Rpm

Bhp

 

1200

 

0.56

1300

 

0.60

1400

 

0.65

1500

 

0.71

1600

 

0.77

1700

 

0.84

1800

 

0.91

1900

1008

0.99

2000

1026

1.08

LEGEND

1.4

Rpm Bhp

1003 0.66

1006 0.71

1012 0.76

1020 0.82

1029 0.89

1041 0.96

1054 1.04

1070 1.12

1086 1.21

1.6

Rpm Bhp

1073 0.76

1075 0.82

1079 0.87

1085 0.94

1093 1.01

1103 1.08

1115 1.16

1129 1.25

1144 1.35

NOTES:

1.82.0

Rpm Bhp Rpm Bhp

1139 0.87 1202 0.98

1140 0.93 1202 1.05

1143 0.99 1204 1.11

1148 1.06 1208 1.18

1155 1.13 1214 1.26

1163 1.21 1221 1.34

1174 1.30 1230 1.43

1186 1.39 1241 1.53

1199 1.49 1253 1.63

Bhp - Brake Horsepower

High Range Motor/Drive Required

1.Motor drive range is 596 to 910 rpm for low range motor/drive, 828 to 1173 rpm for high range motor/drive. All other rpms require a field‐supplied drive.

2.Maximum continuous bhp is 0.85 for low range motor/drive and 1.60 (single phase) and 2.40 (3 phase) for high range motor/drive.

3.See General Fan Performance Notes.

Fan Performance — 48PGD06 Horizontal Units

AIRFLOW

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

0.2

 

 

0.4

 

0.6

0.8

 

1.0

 

(Cfm)

 

 

 

 

 

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

 

1500

521

0.22

628

0.31

718

0.40

 

0.49

 

0.60

1600

546

0.25

649

0.35

737

0.45

 

0.55

 

0.65

1700

572

0.30

671

0.40

757

0.50

 

0.61

 

0.72

1800

599

0.35

695

0.45

777

0.56

 

0.67

 

0.79

1900

627

0.40

719

0.51

799

0.63

 

0.74

 

0.86

2000

655

0.46

745

0.58

822

0.70

 

0.82

 

0.94

2100

684

0.53

771

0.66

846

0.78

 

0.91

 

1.03

2200

714

0.61

797

0.74

871

0.87

 

1.00

1001

1.13

2300

744

0.69

824

0.83

896

0.96

 

1.10

1022

1.24

2400

775

0.78

852

0.92

922

1.06

 

1.21

1045

1.35

2500

806

0.88

880

1.03

948

1.18

1010

1.32

1069

1.47

AIRFLOW

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

1.2

 

 

1.4

 

1.6

1.8

 

2.0

 

(Cfm)

 

 

 

 

 

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

 

1500

 

0.70

1018

0.82

1083

0.93

1146

1.05

1207

1.18

1600

 

0.77

1027

0.88

1091

1.00

1153

1.13

1212

1.26

1700

 

0.83

1039

0.95

1101

1.08

1161

1.21

1219

1.34

1800

 

0.91

1052

1.03

1112

1.16

1171

1.29

1227

1.43

1900

1004

0.99

1066

1.11

1125

1.25

1182

1.38

1238

1.52

2000

1022

1.07

1082

1.20

1139

1.34

1195

1.48

1249

1.62

2100

1040

1.17

1099

1.30

1155

1.44

1209

1.59

1262

1.73

2200

1060

1.27

1117

1.41

1172

1.55

1225

1.70

1277

1.85

2300

1081

1.38

1136

1.52

1190

1.67

1242

1.82

1292

1.98

2400

1102

1.50

1156

1.65

1209

1.80

1259

1.96

1309

2.12

2500

1124

1.62

1177

1.78

1228

1.94

1278

2.10

1326

2.26

LEGEND

 

 

 

 

NOTES:

 

 

 

 

Bhp - Brake Horsepower

 

 

 

 

1.

Motor drive range is 690 to 978 rpm for low range motor/drive and 929 to 1261 rpm

 

 

 

 

 

for high range motor/drive. All other rpms require a field‐supplied drive.

 

2. Maximum continuous bhp is 0.85 (single phase) and 2.40 (3 phase) for low range motor/drive and 1.60 (single phase) and 2.40 (3 phase) for high range motor/drive. 3. See General Fan Performance Notes.

130

Page 130
Image 130
Carrier 48/50PG C03-14 manual Fan Performance — 48PGF05 Horizontal Units, Fan Performance — 48PGD06 Horizontal Units