Agilent Technologies 5951-2826, 5951-2827 manual Application Connections

Page 44

Application Connections

Wiring Considerations

FIRE HAZARD To satisfy safety requirements, load wires must be heavy enough not to overheat while carrying the short-circuit output current of the device connected to the Electronic Load. Refer to Table 3-1 for the ampere capacity of various stranded wire sizes.

Input connections are made to the + and - binding posts on the panel. (Input connections can also be made to the optional front panel binding posts). A major consideration in making input connections is the wire size. The minimum wire size required to prevent overheating may not be large enough to maintain good regulation. It is recommended that stranded, copper wires be used. The wires should be large enough to limit the voltage drop to no more than 0.5 V per lead. Table 3-2 gives the maximum load lead length to limit the voltage drop to the specified limit.

Local Sense Connections

Figure 3-11 illustrates a typical setup with Electronic Load connected for constant current or constant resistance operation. Local sensing is used in applications where lead lengths are relatively short, or where load regulation is not critical. The sense switch must be set to LCL. Load leads should be bundled or tie-wrapped together to minimize inductance.

Remote Sense Connections

Figure 3-12 illustrates a typical setup with Electronic Load connected for remote sense operation. The remote sense terminals of Electronic Load are connected to the output of the power supply. Remote sensing compensates for the voltage drop in applications that require long lead lengths. It is only useful when Electronic Load is operating in CV or CR mode, or when using voltage readback. The sense switch must be set to RMT. Load leads should be bundled or tie wrapped together to minimize inductance.

Table 3-1. Stranded Copper Wire Ampere Capacity

Wire Size

AWG

22

20

18

16

14

12

10

8

6

4

Cross Section Area in mm2

0.75

1

1.5

2.5

4

6

10

Ampacity

5.0

8.33

10

15.4

13.5

19.4

16

31.2

25

40

32

55

40

75

63

100

135

Notes:

1. Ratings for AWG-sized wires derived from MIL-W-5088B. Ratings for metric-sized wires derived from IEC Publication

33-51.

.

2. Ampacity of aluminum wire is approximately 84% of that listed for copper wire.

3. When two or more wires are bundled together, ampacity for each wire must be reduced to the following percentages:

2 conductors 94%

3 conductors 89%

4 conductors 83%

5 conductors 76%

4.Maximum temperatures: Ambient = 50° C Conductor = 105° C

44 Installation

Image 44
Contents Agilent Part No Microfiche Part No Updated April Operating ManualCertification Safety Summary Safety Summary Symbol DescriptionHerstellerbescheinigung Manufacturer’s DeclarationPrinting History Table of Contents Calibration Local OperationRemote Operation Considerations for Operating in Constant Resistance Mode What’s In This Manual Reader PathOptions General InformationSafety Requirements SpecificationsRegulation Constant Resistance Mode Ranges Modes Continuous ModePulsed Mode 6060B 6063BCurrent Readback Temperature Coefficient Supplemental Characteristics 6060B 6063BResolution Maximum Readback Capability BandwidthSupplemental Characteristics Maximum VA Peak Inrush Current 2.5 a typicalCurrent Slew Rate Rate # High Range Step Low Range Step Transition TimeModel 6063B Range Transient Current Level Resistance Slew RateOvershoot 6060B 6063B 10% With unit onWith unit off WidthPage Introduction Front Panel DescriptionRemote Programming Operation OverviewLocal/Remote Control Programmable FeaturesConstant Current CC Mode Modes of OperationTriggered Current Level Software Current LimitImmediate Resistance Level Constant Resistance CR ModeSlew Rate Transient Resistance Level Constant Voltage CV ModeTriggered Resistance Level Immediate Voltage Level Triggered Voltage LevelTransient Voltage Level Transient OperationHpsl Command Description Pulsed Transient OperationSelects the external trigger input Selects pulsed transient operationSets pulse width to 1 millisecond Selects the external trigger input sourceTriggering a preset level Triggering a transient pulseToggling Slew Rate And Minimum Transition TimeInput Current, Voltage, and Power Measurement Risetime Transition LimitationShort On/Off Transition Times and Slew RatesSaving and Recalling Settings Reading Remote Programming ErrorsInput On/Off Status ReportingProtection Features Resetting Latched ProtectionOvervoltage OvercurrentControl Connector OverpowerOvertemperature Reverse VoltageExternal Programming Input FaultMonitor Outputs Port On/Off Inspection Check Line Voltage Location and CoolingTurn-On Checkout Voltage Select Switches Line Voltage Fuse Agilent Part NoConnect The Power Cord Gpib Errors Input Errors Display DescriptionError Turn-On/SelftestController Connection Power TestGpib Connector Rear Panel Connectors and Switches Wire Size Strip backGpib Address AWGInput Binding Post Control Connector Pins 3 +S and -SIM and VM CommonTrigger Connector Sense SwitchApplication Connections Zero-Volt Loading Connections Maximum Wire Lengths to Limit Voltage DropsParallel Connections 11. Local Sensing 13. Parallel Operation Page Front Panel Controls and Indicators Description Local OperationControls and Indicators Description Function Keys Local Control Overview Turning the Input On/Off Using The Function Keys∙ Short on Recommended Programming Sequence Setting the Mode of Operation Setting CC ValuesCC Programming Ranges Function Key DisplayExamples Setting CR Values Examples Setting CV Values Continuous Pulse Train Programming Ranges Function Key Display Range of ValuesUsing The System Keys Shorting The InputSetting The Electronic Load’s Gpib Address Displaying Error CodesFactory Default Settings Function 6060B 6063B Changing Wake-up SettingsRecalling the Factory Default Values Enter/Output Statements Gpib AddressOutput EnterSending a Remote Command Remote Programming CommandsGetting Data Back Output 705 MEASCURR?Modes RangesTransient levels Slew RatesRemote Programming Flowchart Sheet Remote Programming Flowchart Sheet CR Mode Example CC Mode ExampleCV Mode Example Continuous Transient Operation Example Pulsed Transient Operation ExampleHpsl Command Short Form Output 705TRAN on Output 705INPUT onRemote Programming Ranges Function Constant Current CCConstant Resistance CR 6060BConstant Voltage CV Transient OperationPage Equipment Characteristics Recommended Model Example ProgramsEquipment Required Equipment Required for CalibrationCalibration Commands Calibration Flowcharts Example ProgramSupply Shunt Values Settings Calibration Information 6060B 6063BCalibration Flowchart Calibration Flowchart Calibration Flowchart Program Listing PauseWait END ifPause Subend Print Voltage CalibrationElse Explanation LinePage Considerations For Operating In Constant Resistance Mode Considerations For Operating In Constant Resistance ModeConsiderations For Operating In Constant Resistance Mode Index IndexIndex 24, 25, 26 Index Agilent Sales and Support Offices Agilent Sales and Support OfficeManual Updates