Agilent Technologies 5951-2826 manual Considerations For Operating In Constant Resistance Mode

Page 88

If large resistances are required, the accuracy can be improved by reading the voltage and current directly from the load, calculating the actual resistance, and then adjusting the programmed value accordingly. This technique is most practical in applications requiring a fixed resistive load.

The following examples illustrate the worst-case error possibilities resulting from op amp offsets. The examples are based on a 300-watt unit having 1 ohm, 1 kilohm, and 10 kilohm ranges. These examples do not include the effects of gain errors on accuracy (specified in percent).

Note

Note that typical performance is far better than the worst-case possibilities shown here.

Example 1: 1 Ω range (0.033 Ω to 1 Ω)

The offset error for this range is specified as + 8 milliohms. Therefore, if 1 ohm is programmed, the actual resistance will be

1 Ω + 0.008 Ω = 0.992 to 1.008 Ω.

Similarly, if 0.033 ohms is programmed, the actual resistance will be

0.033 Ω ± 0.008 Ω = 0.032 to 0.048 Ω.

Example 2: 1 kΩ range: (1 Ω to 1 kΩ, or 1 S to 0.001 S)

Because this range is, in effect, a constant conductance range, offset is specified in siemens (1/ohms). Resistance, however, is programmed in ohms. Therefore, to compute the contribution of offset error to programmed value error, the programmed value must be reciprocated first. The offset is then applied to the programmed value (in siemens) and the result is once again reciprocated.

Note that 1 ohm equals 1 siemen, and 1 kilohm equals 0.001 siemens. Therefore, the conductance (0.001 siemens) at full scale resistance (1 kilohm) is a very small percentage of scale conductance.

If 1 ohm is programmed, the corresponding conductance value is 1 siemen. The actual resistance will be 1 S ± 0.008 S = 1.008 S to 0.992 S

= 0.992 Ω to 1.008 Ω

If 1 kilohm is programmed, the corresponding conductance value is 0.001 siemens. The actual resistance will be 0.001 S ± 0.008 S = 0.009 S to -0.007 S

=111 Ω to infinite Ω (typically 900 to 1100 Ω)

The load cannot provide negative current corresponding to negative siemens. Therefore, zero current translates to zero siemens, which corresponds to infinite ohms. Note also that the resistance can be as low as 111 ohms, which is much lower than 1 kilohm. This is because the current offset is large compared to the small current corresponding to 1 kilohm (0.001 siemens). For instance, 0.001 siemens corresponds to 6 milliamps at 6 volts input, and the offset specification of 0.008 siemens corresponds to 48 milliamps at 6 volts input.

Calculations for the 10 kilohm range are similar.

88 Considerations For Operating In Constant Resistance Mode

Image 88
Contents Agilent Part No Microfiche Part No Updated April Operating ManualCertification Safety Summary Safety Summary Symbol DescriptionHerstellerbescheinigung Manufacturer’s DeclarationPrinting History Table of Contents Remote Operation Local OperationCalibration Considerations for Operating in Constant Resistance Mode What’s In This Manual Reader PathOptions General InformationSafety Requirements SpecificationsRegulation Constant Resistance Mode Ranges Modes Continuous ModePulsed Mode 6060B 6063BCurrent Readback Resolution Supplemental Characteristics 6060B 6063BTemperature Coefficient Maximum Readback Capability BandwidthSupplemental Characteristics Maximum VA Peak Inrush Current 2.5 a typicalCurrent Slew Rate Rate # High Range Step Low Range Step Transition TimeOvershoot Resistance Slew RateModel 6063B Range Transient Current Level 6060B 6063B 10% With unit onWith unit off WidthPage Introduction Front Panel DescriptionRemote Programming Operation OverviewLocal/Remote Control Programmable FeaturesConstant Current CC Mode Modes of OperationTriggered Current Level Software Current LimitSlew Rate Constant Resistance CR ModeImmediate Resistance Level Triggered Resistance Level Constant Voltage CV ModeTransient Resistance Level Immediate Voltage Level Triggered Voltage LevelTransient Voltage Level Transient OperationHpsl Command Description Pulsed Transient OperationSelects the external trigger input Selects pulsed transient operationSets pulse width to 1 millisecond Selects the external trigger input sourceTriggering a preset level Triggering a transient pulseToggling Slew Rate And Minimum Transition TimeInput Current, Voltage, and Power Measurement Risetime Transition LimitationShort On/Off Transition Times and Slew RatesSaving and Recalling Settings Reading Remote Programming ErrorsInput On/Off Status ReportingProtection Features Resetting Latched ProtectionOvervoltage OvercurrentControl Connector OverpowerOvertemperature Reverse VoltageMonitor Outputs FaultExternal Programming Input Port On/Off Inspection Turn-On Checkout Location and CoolingCheck Line Voltage Voltage Select Switches Line Voltage Fuse Agilent Part NoConnect The Power Cord Gpib Errors Input Errors Display DescriptionError Turn-On/SelftestGpib Connector Power TestController Connection Rear Panel Connectors and Switches Wire Size Strip backGpib Address AWGInput Binding Post Control Connector Pins 3 +S and -SIM and VM CommonTrigger Connector Sense SwitchApplication Connections Parallel Connections Maximum Wire Lengths to Limit Voltage DropsZero-Volt Loading Connections 11. Local Sensing 13. Parallel Operation Page Front Panel Controls and Indicators Description Local OperationControls and Indicators Description Function Keys Local Control Overview ∙ Short on Using The Function KeysTurning the Input On/Off Recommended Programming Sequence Setting the Mode of Operation Setting CC ValuesCC Programming Ranges Function Key DisplayExamples Setting CR Values Examples Setting CV Values Continuous Pulse Train Programming Ranges Function Key Display Range of ValuesUsing The System Keys Shorting The InputSetting The Electronic Load’s Gpib Address Displaying Error CodesFactory Default Settings Function 6060B 6063B Changing Wake-up SettingsRecalling the Factory Default Values Enter/Output Statements Gpib AddressOutput EnterSending a Remote Command Remote Programming CommandsGetting Data Back Output 705 MEASCURR?Modes RangesTransient levels Slew RatesRemote Programming Flowchart Sheet Remote Programming Flowchart Sheet CV Mode Example CC Mode ExampleCR Mode Example Continuous Transient Operation Example Pulsed Transient Operation ExampleHpsl Command Short Form Output 705TRAN on Output 705INPUT onRemote Programming Ranges Function Constant Current CCConstant Resistance CR 6060BConstant Voltage CV Transient OperationPage Equipment Characteristics Recommended Model Example ProgramsEquipment Required Equipment Required for CalibrationCalibration Commands Calibration Flowcharts Example ProgramSupply Shunt Values Settings Calibration Information 6060B 6063BCalibration Flowchart Calibration Flowchart Calibration Flowchart Program Listing PauseWait END ifPause Subend Print Voltage CalibrationElse Explanation LinePage Considerations For Operating In Constant Resistance Mode Considerations For Operating In Constant Resistance ModeConsiderations For Operating In Constant Resistance Mode Index IndexIndex 24, 25, 26 Index Agilent Sales and Support Offices Agilent Sales and Support OfficeManual Updates