Agilent Technologies 5951-2826 manual Location and Cooling, Turn-On Checkout, Check Line Voltage

Page 36

Location and Cooling

Table 1-1 gives the dimensions of the Electronic Load. The cabinet has plastic feet that are shaped to ensure self-alignment when stacked with other Agilent System II cabinets. The feet may be removed for rack mounting. Your Electronic Load must be installed in a location that allows sufficient space at the sides and rear of the unit for adequate air circulation.

The unit can be mounted in a standard 19-inch rack panel or enclosure. Rack mount kits are available as option numbers 908 and 909 (with handles). Installation instructions are included with each rack mounting kit. Instrument support rails are recommended for non-stationary installations.

The unit can operate without loss of performance within the temperature range of 0° to 40°C, and with derated performance from 40° to 55° C. A variable-speed fan cools the unit by drawing in air through the sides and exhausting it out the back. Using Agilent rack mount or slide kits will not impede the flow of air.

Turn-On Checkout

The simplified turn-on checkout procedure discussed in this section verifies that about 90% of the Electronic Load is operating correctly. The Service Manual (Option 910) contains detailed performance and verification tests. Before connecting the power cord and turning on the Electronic Load, check that the line voltage is set correctly and that the sense switch is set to Local.

Check Line Voltage

Your Electronic Load can operate with a 100, 120, 220, or 240 Vac input as indicated on the label on the rear panel (see Figure 3-2). Make sure that the factory check mark corresponds to your nominal line voltage. Skip this procedure if the label is correctly marked.

Figure 3-2. Line Label

1.With the unit off, disconnect the power cord and remove the four cover screws (M5). Use a number 2 Pozidriv.

2.Locate the voltage select switches S552 and S553 in the unit (see Figure 3-3).

3.Refer to the drawing on the PC board next to the switches and set the switches to the proper voltage.

4.Replace the cover and mark the correct voltage on the rear panel label.

5.Check the rating of the line fuse and replace it with the correct fuse if necessary (see next step).

6.The line fuse is located below the ac line receptacle (see Figure 3-4). With the power cord removed, use a small screwdriver to extract the fuseholder from under the ac socket. Replace the fuse with the appropriate type as indicated below. These are time-delay fuses.

36 Installation

Image 36
Contents Agilent Part No Microfiche Part No Updated April Operating ManualCertification Safety Summary Safety Summary Symbol DescriptionHerstellerbescheinigung Manufacturer’s DeclarationPrinting History Table of Contents Local Operation Remote OperationCalibration Considerations for Operating in Constant Resistance Mode What’s In This Manual Reader PathOptions General InformationSafety Requirements SpecificationsRegulation Constant Resistance Mode Ranges Modes Continuous ModePulsed Mode 6060B 6063BCurrent Readback Supplemental Characteristics 6060B 6063B ResolutionTemperature Coefficient Maximum Readback Capability BandwidthSupplemental Characteristics Maximum VA Peak Inrush Current 2.5 a typicalCurrent Slew Rate Rate # High Range Step Low Range Step Transition TimeResistance Slew Rate OvershootModel 6063B Range Transient Current Level 6060B 6063B 10% With unit onWith unit off WidthPage Introduction Front Panel DescriptionRemote Programming Operation OverviewLocal/Remote Control Programmable FeaturesConstant Current CC Mode Modes of OperationTriggered Current Level Software Current LimitConstant Resistance CR Mode Slew RateImmediate Resistance Level Constant Voltage CV Mode Triggered Resistance LevelTransient Resistance Level Immediate Voltage Level Triggered Voltage LevelTransient Voltage Level Transient OperationHpsl Command Description Pulsed Transient OperationSelects the external trigger input Selects pulsed transient operationSets pulse width to 1 millisecond Selects the external trigger input sourceTriggering a preset level Triggering a transient pulseToggling Slew Rate And Minimum Transition TimeInput Current, Voltage, and Power Measurement Risetime Transition LimitationShort On/Off Transition Times and Slew RatesSaving and Recalling Settings Reading Remote Programming ErrorsInput On/Off Status ReportingProtection Features Resetting Latched ProtectionOvervoltage OvercurrentControl Connector OverpowerOvertemperature Reverse VoltageFault Monitor OutputsExternal Programming Input Port On/Off Inspection Location and Cooling Turn-On CheckoutCheck Line Voltage Voltage Select Switches Line Voltage Fuse Agilent Part NoConnect The Power Cord Gpib Errors Input Errors Display DescriptionError Turn-On/SelftestPower Test Gpib ConnectorController Connection Rear Panel Connectors and Switches Wire Size Strip backGpib Address AWGInput Binding Post Control Connector Pins 3 +S and -SIM and VM CommonTrigger Connector Sense SwitchApplication Connections Maximum Wire Lengths to Limit Voltage Drops Parallel ConnectionsZero-Volt Loading Connections 11. Local Sensing 13. Parallel Operation Page Front Panel Controls and Indicators Description Local OperationControls and Indicators Description Function Keys Local Control Overview Using The Function Keys ∙ Short onTurning the Input On/Off Recommended Programming Sequence Setting the Mode of Operation Setting CC ValuesCC Programming Ranges Function Key DisplayExamples Setting CR Values Examples Setting CV Values Continuous Pulse Train Programming Ranges Function Key Display Range of ValuesUsing The System Keys Shorting The InputSetting The Electronic Load’s Gpib Address Displaying Error CodesFactory Default Settings Function 6060B 6063B Changing Wake-up SettingsRecalling the Factory Default Values Enter/Output Statements Gpib AddressOutput EnterSending a Remote Command Remote Programming CommandsGetting Data Back Output 705 MEASCURR?Modes RangesTransient levels Slew RatesRemote Programming Flowchart Sheet Remote Programming Flowchart Sheet CC Mode Example CV Mode ExampleCR Mode Example Continuous Transient Operation Example Pulsed Transient Operation ExampleHpsl Command Short Form Output 705TRAN on Output 705INPUT onRemote Programming Ranges Function Constant Current CCConstant Resistance CR 6060BConstant Voltage CV Transient OperationPage Equipment Characteristics Recommended Model Example ProgramsEquipment Required Equipment Required for CalibrationCalibration Commands Calibration Flowcharts Example ProgramSupply Shunt Values Settings Calibration Information 6060B 6063BCalibration Flowchart Calibration Flowchart Calibration Flowchart Program Listing PauseWait END ifPause Subend Print Voltage CalibrationElse Explanation LinePage Considerations For Operating In Constant Resistance Mode Considerations For Operating In Constant Resistance ModeConsiderations For Operating In Constant Resistance Mode Index IndexIndex 24, 25, 26 Index Agilent Sales and Support Offices Agilent Sales and Support OfficeManual Updates