Installation Instructions | IM584000300 |
Spec. No. 584000300 (Model | Issue AB, April 3, 2013 |
|
|
External Battery Connections (if required)
Danger: Adhere to the “Important Safety Instructions” presented at the front of this document. DO NOT attempt to work on an energized system.
Warning: Observe proper polarity when making battery connections.
Up to five internal or external battery strings can be connected to busbars located in the power and control
Connect any external battery strings to the positive and negative battery connection points per Figure
If there is a battery breaker associated with the external battery string that is to be controlled (tripped) by the system’s LVD circuit, wire per Figure
Use 22 AWG (0.5mm2) wire.
The mating connector for the alarm/control connector on the power and control
The mating contacts for the alarm/control connector on the power and control
The contacts are to be crimped with Tyco hand tool P/N 724651.
External battery breaker requirements are as follows.
External battery breaker must contain a 48V shunt trip with the following specifications.
a)Rated Voltage: 12 to 60 VDC.
b)Maximum Release Duration: ≤ 10ms.
c)Minimum Resistance: >1 ohm.
External battery breaker must contain auxiliary contacts that are normally closed if the breaker is close. Minimum contact rating is 48V DC at 2A.
Chapter 3. Making Electrical Connections | Page 33 |
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.