Installation Instructions | IM584000300 |
Spec. No. 584000300 (Model | Issue AB, April 3, 2013 |
|
|
TASKS TO BE PERFORMED FOR CUSTOMER INTEGRATED SYSTEMS
ALSO MAKE THE CONNECTIONS DESCRIBED UNDER “Tasks to Be Perform for All Installations” STARTING ON PAGE 25.
Grounding
Danger: Failure to follow proper grounding procedures can result in electric shock hazard to personnel or the risk of fire, should a ground fault occur.
For grounding requirements, refer to the current edition of the American National Standards Institute (ANSI) approved National Fire Protection Association's (NFPA) National Electrical Code (NEC), applicable local codes, and your specific site requirements. For operation in countries where the NEC is not recognized, follow applicable codes.
Refer to Figure
Sub-Rack Grounding (Frame Ground)
When individual system components are furnished, the individual components must be grounded on site by the customer after installation into an IT rack. A cabinet grounding stud is located on the rear of the power and control
NPG Configurations Only: Return Busbar
The return busbar
HRMG Configurations Only: Bus Grounding Connection
A lead exits the rear of the power and control
Caution: Failure to terminate this conductor to ground will render the system ground fault detection circuit and the ±200V DC voltage reference inoperable. It is essential to properly bond this lead to ground.
Note: This lead is 16 AWG, approximately 100” long, and terminated in a ring lug with a 1/4” clearance hole.
Chapter 3. Making Electrical Connections | Page 17 |
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.