Installation Instructions | IM584000300 |
Spec. No. 584000300 (Model | Issue AB, April 3, 2013 |
|
|
IB2 (ACU+ Controller Interface Board) Connections (if required)
The IB2 (ACU+ Controller Interface Board) provides connection points for digital inputs, programmable relay outputs, and temperature probes. The IB2 interface board is accessed from the front of the power and control
When connecting input and output wires to the IB2 board, route the leads through the opening provided on the top of the power and control
Note: The IB2 board is isolated from the system’s 400VDC bus and the internal 48V bias supplies. If a voltage potential is required to be connected to digital inputs and/or relay contacts, customer must supply the voltage source.
Digital Inputs and Programmable Relay Outputs
Digital input and relay output leads are connected to
Digital Inputs
Connect up to eight (8) digital inputs to the IB2 (ACU+ Controller Interface Board). Note that you must supply both paths for the digital input (either a positive or negative signal and the opposite polarity return path). Observe proper polarity. Refer to Figure
The digital inputs can be programmed to provide an alarm when the signal is applied (HIGH) or removed (LOW). Refer to the ACU+ Controller Operation Instructions
Digital Input Ratings: Refer to the following.
a)Maximum Voltage Rating: 60V DC.
b)Active High: > 19V DC.
c)Active Low: < 1V DC.
Programmable Relay Outputs
The IB2 provides eight programmable alarm relays with dry
Relay Ratings: Refer to the following.
a)1A Steady State @ 30V DC.
b)3A Peak @ 30V DC.
Chapter 3. Making Electrical Connections | Page 35 |
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.