Schneider Electric 66074, 66846 user manual 23/81

Page 23

Network

Management Card

User Manual

The shutdown sequences take into account the time required for the registered servers to shut down without losing data (see shutdown parameters ). Once the sequence has started, the commands are disabled until it ends.

After a startup sequence, the commands are disabled for 120 seconds to enable the servers to fully restart

The Check column proposes six different commands, and a command is only actually started after clicking on 'Execute':

“Safe power down”: a sequence to switch off output power is launched immediately. The symbol representing the output flashes, indicating that the sequence is in progress. The systems supplied are shut down correctly while the shutdown sequence is running, then the output is cut.

“Safe power down & reboot”: A sequence to switch off then restore output power is launched immediately. The symbol representing the output flashes, indicating that the shutdown sequence is in progress. The powered systems are shut down correctly during the shutdown sequence, then the output is switched off. Finally, the restart sequence is launched at the end of the time delay specified in the “Toggle duration” parameter. The output status is updated.

Immediate On”: a sequence to switch on output power is launched immediately. The output is re-powered and the systems supplied start up again correctly.

Delayed, safe power down”: this is the same switch off sequence as for the “ Safe power down ” command, but postponed by the number of seconds programmed in the “Off Delay” parameter.

Delayed, safe power down & reboot:” this is the same switch off then on sequence as for the Safe power down & reboot ” command, but postponed by the number of seconds programmed in the “ Off Delay ” parameter.

Delayed On ”: this is the same switch on sequence as for the “ Immediate On ” command, but postponed by the number of seconds programmed in the “ On Delay ” parameter.

The Save button saves the Off Delay, Toggle duration and On Delay parameters on the card .

Security: The administrator must click on Save and enter his login / password to save modifications or run

commands. The login and password by default are: MGEUPS.

Network Management Card – User Manual

34003676EN/HA

Page 23/81

Image 23
Contents Network Management Card NMC Transverse Environment Sensor Network Management Card Appendices Tables of Alarms and Events ConfigurationConfiguration VIA Telnet Configuration VIA SSH MAINTENANCE72 Software UpgradeGlossary Network Management Card Connecting the UPS / STS to the NetworkIntroduction Network Shutdown module only available for UPS, not for STS MGE supervisor Enterprise Power ManagerProtecting the computers / servers Monitoring the UPSs over the networkPresentation of the Network Management Cards NMC How to connect UPS / networkSetting up the protection, for UPS only ConnectionSending text messages SMS Presentation of the Environment Sensor solutionDirect sending of E-mail Technical data 10/81 Environment Sensor InstallationBasic configuration Optimising the performance of your browser Supervision / Administration via a Web browserUPS status zone essential information UPS / STSUPS properties UPS zone general information on the UPSBattery status zone STS status zone essential information STS propertiesSTS zone general information on the STS Sources status zone AboutOn-line help 18/81 Normal input measurements UPS 3-Phase displayBy Pass measurements Battery measurementsSTS 3-Phase display Source 2 input measurement UPS Control23/81 UPS weekly schedule programming Important note Shutdown parametersViewing the alarms UPS Measurements LogsSTS Measurements 29/81 STS Event log UPS Event log31/81 System log 33/81 Notified events NotificationUPS Email Notification Recipient List Mail message configuration see nextSTS Email Notification Other settingsSubject Email Message SettingsUPS Email Message Settings SenderSTS Email Message Settings Email Example User Name and password by default are Mgeups ConfigurationNetwork Settings 42/81 System 44/81 UPS Notified Applications 46/81 Central Shutdown Configuration STS Notified Applications 49/81 Access control 51/81 Access is disabled and the card is accessible in SSH Time Environment CharacteristicsStatus Configuration Log Environment status 56/81 UPS Environment Settings UPS Environment SettingsHumidity STS Environment Settings4 Log Shutdown criteria managed by the Management Card Set-up of the shutdown parametersShutdown duration Specific set-up for long autonomy installation 30 mnShutdown when backup time is less than Different server and UPS shutdown sequences 63/81 4 Off/On command Configuration in local mode Configuring a set of cards with MupgradeMgeups Choice 1 Snmp agent configuration menuChoice 2 UPS / STS parameters Choice 3 Access controlChoice 5 Reset the card Choice 4 Restore default configurationPuTTY SSH Client Program Configuration via TelnetConfiguration via SSH 70/81 71/81 Card software upgrade via Tftp Unix and Windows Software upgradeCard firmware upgrade using Mupgrade Windows English French Tables of alarms and eventsUPS Alarm table STS Alarm tableUPS event table UPS STS event table 77/81 System alarm table Glossary Telnet Subnet maskTrap Snmp