Schneider Electric 66074, 66846 user manual UPS Notified Applications

Page 45

Network

Management Card

User Manual

3.5.3 UPS Notified Applications

Click the “Notified Application” section in the menu.

Security: the administrator has to enter his login/password to view this information.

This menu enables:

The addition of the supervision stations receiving traps and configuration of the trap type.

To list all the Notified Applications and the main parameters.

Simulate events to test notification and shutdown of the Notified Applications.

Up to 50 destinations can be managed by the card.

The card is compatible with the Network Shutdown Module

Note: It is not necessary to add the Network Shutdown Modules protecting your servers in this list as it is done automatically.

Select an entry in the list to modify the values in the edit zone at the bottom of the page. Note that the Network Shutdown Module must not be manually modified.

The applications in the table appears in the order they have subscribed to the card. Following informations are displayed :

Nr : is the index where the application is stored into the table.

Hostname or IP Address : By priority the hostname of the computer is displayed when the IP address can be converted into a hostname with a DNS server or if the application has been entered as a hostname (see page Network Management System settings). Otherwise the IP address is displayed.

Application Name : sent by the application at subscribe time or manually entered.

Output : is the number of the output from which the client is powered.

Configuration : shows where the parameters of Network Shutdown Module comes from : Local(coming from the application) or Central(coming from the card).

The Central Shutdown Configuration is available by clicking on Configuration link.

Shutdown duration : is the shutdown duration necessary to properly shutdown the computer.

Network Management Card – User Manual

34003676EN/HA

Page 45/81

Image 45
Contents Network Management Card NMC Transverse Environment Sensor Network Management Card Configuration VIA Telnet Configuration VIA SSH ConfigurationMAINTENANCE72 Software Upgrade Appendices Tables of Alarms and EventsGlossary Connecting the UPS / STS to the Network IntroductionNetwork Management Card Protecting the computers / servers MGE supervisor Enterprise Power ManagerMonitoring the UPSs over the network Network Shutdown module only available for UPS, not for STSSetting up the protection, for UPS only How to connect UPS / networkConnection Presentation of the Network Management Cards NMCPresentation of the Environment Sensor solution Direct sending of E-mailSending text messages SMS Technical data 10/81 Installation Basic configurationEnvironment Sensor Optimising the performance of your browser Supervision / Administration via a Web browserUPS properties UPS / STSUPS zone general information on the UPS UPS status zone essential informationBattery status zone STS properties STS zone general information on the STSSTS status zone essential information Sources status zone AboutOn-line help 18/81 Normal input measurements UPS 3-Phase displayBy Pass measurements Battery measurementsSTS 3-Phase display Source 2 input measurement UPS Control23/81 UPS weekly schedule programming Important note Shutdown parametersViewing the alarms UPS Measurements LogsSTS Measurements 29/81 STS Event log UPS Event log31/81 System log 33/81 Notification UPS Email NotificationNotified events Recipient List Mail message configuration see nextSTS Email Notification Other settingsUPS Email Message Settings Email Message SettingsSender SubjectSTS Email Message Settings Email Example User Name and password by default are Mgeups ConfigurationNetwork Settings 42/81 System 44/81 UPS Notified Applications 46/81 Central Shutdown Configuration STS Notified Applications 49/81 Access control 51/81 Access is disabled and the card is accessible in SSH Time Characteristics Status Configuration LogEnvironment Environment status 56/81 UPS Environment Settings UPS Environment SettingsHumidity STS Environment Settings4 Log Shutdown criteria managed by the Management Card Set-up of the shutdown parametersSpecific set-up for long autonomy installation 30 mn Shutdown when backup time is less thanShutdown duration Different server and UPS shutdown sequences 63/81 4 Off/On command Configuration in local mode Configuring a set of cards with MupgradeMgeups Choice 1 Snmp agent configuration menuChoice 2 UPS / STS parameters Choice 3 Access controlChoice 5 Reset the card Choice 4 Restore default configurationConfiguration via Telnet Configuration via SSHPuTTY SSH Client Program 70/81 71/81 Software upgrade Card firmware upgrade using Mupgrade WindowsCard software upgrade via Tftp Unix and Windows UPS Alarm table Tables of alarms and eventsSTS Alarm table English FrenchUPS event table UPS STS event table 77/81 System alarm table Glossary Telnet Subnet maskTrap Snmp