Schneider Electric 66846, 66074 user manual Environment, Characteristics, Status Configuration Log

Page 54

Network

Management Card

User Manual

list. Connection is made with the server and the date and time are set after clicking on the “Save” button. Time is updated every hour.

The card uses the NTP protocol (UDP 123 port) and the firewall must be set accordingly, no error message is generated if the time server contact fails

Daylight Saving Time: Enables corrections due to summer / winter time changes, this option must be supported by the NTP server.

Note 1:

Time drift is related to card electronics. It may be up to a maximum of +/- 2min/month.

3.6Environment

The environment sensor is an option that enables temperature and humidity to be measured, and indication of the position of two external contacts. It is connected with a standard network cable to the Card Settings port of the Network Management Card.

On startup, the card automatically detects sensor presence. The main menu then displays an additional section “Environment” with the following elements:

Status

Configuration

Log

Note 1 This function is only accessible with the DA version software (or superior) for the card. This software can be downloaded on the www.apc.com site, from the download section.

Note 2: To switch the serial port to the configuration mode, just disconnect the sensor cable and reinitialise the card by pressing “Reset”. The reverse operation must be performed to manage the environment sensor once again.

3.6.1 Characteristics

Temperature measurement from 0 to 70 °C with +/- 1° C accuracy

Humidity measurement from 0 to 100 % with +/- 6 % accuracy

Min. / max. time-stamped function for temperature and humidity

Choice of displaying temperature in Celsius or Fahrenheit

High and low thresholds, hysteresis and offset adjustment via Web interface

Possibility of notification of status changes by e-mail, SMS or SNMP trap

Position detection of 2 dry contacts (maximum sensor/contact distance: 20m)

Network Management Card – User Manual

34003676EN/HA

Page 54/81

Image 54
Contents Network Management Card NMC Transverse Environment Sensor Network Management Card MAINTENANCE72 Software Upgrade ConfigurationConfiguration VIA Telnet Configuration VIA SSH Appendices Tables of Alarms and EventsGlossary Connecting the UPS / STS to the Network IntroductionNetwork Management Card Monitoring the UPSs over the network MGE supervisor Enterprise Power ManagerProtecting the computers / servers Network Shutdown module only available for UPS, not for STSConnection How to connect UPS / networkSetting up the protection, for UPS only Presentation of the Network Management Cards NMCPresentation of the Environment Sensor solution Direct sending of E-mailSending text messages SMS Technical data 10/81 Installation Basic configurationEnvironment Sensor Supervision / Administration via a Web browser Optimising the performance of your browserUPS zone general information on the UPS UPS / STSUPS properties UPS status zone essential informationBattery status zone STS properties STS zone general information on the STSSTS status zone essential information About Sources status zoneOn-line help 18/81 UPS 3-Phase display Normal input measurementsBattery measurements By Pass measurementsSTS 3-Phase display UPS Control Source 2 input measurement23/81 UPS weekly schedule programming Shutdown parameters Important noteViewing the alarms Logs UPS MeasurementsSTS Measurements 29/81 UPS Event log STS Event log31/81 System log 33/81 Notification UPS Email NotificationNotified events Mail message configuration see next Recipient ListOther settings STS Email NotificationSender Email Message SettingsUPS Email Message Settings SubjectSTS Email Message Settings Email Example Configuration User Name and password by default are MgeupsNetwork Settings 42/81 System 44/81 UPS Notified Applications 46/81 Central Shutdown Configuration STS Notified Applications 49/81 Access control 51/81 Access is disabled and the card is accessible in SSH Time Characteristics Status Configuration LogEnvironment Environment status 56/81 UPS Environment Settings UPS Environment SettingsSTS Environment Settings Humidity4 Log Set-up of the shutdown parameters Shutdown criteria managed by the Management CardSpecific set-up for long autonomy installation 30 mn Shutdown when backup time is less thanShutdown duration Different server and UPS shutdown sequences 63/81 4 Off/On command Configuring a set of cards with Mupgrade Configuration in local modeChoice 1 Snmp agent configuration menu MgeupsChoice 3 Access control Choice 2 UPS / STS parametersChoice 4 Restore default configuration Choice 5 Reset the cardConfiguration via Telnet Configuration via SSHPuTTY SSH Client Program 70/81 71/81 Software upgrade Card firmware upgrade using Mupgrade WindowsCard software upgrade via Tftp Unix and Windows STS Alarm table Tables of alarms and eventsUPS Alarm table English FrenchUPS event table UPS STS event table 77/81 System alarm table Glossary Subnet mask TelnetTrap Snmp