Network
Management Card
User Manual
1.7Technical data
1.7.1 Configuration
The user can configure the card with one of the following means:
◗Web browser
◗Local serial link
◗Telnet console
◗BOOTP/DHCP
◗Mupgrade
1.7.2 Administration
◗Up to 50 workstations protected
◗Up to 15 browsers connected at the same time
◗
◗Measurement of temperature and humidity, adjustable thresholds, possibility of sending
◗Control of UPS on/off switching via the HTML interface
◗Adjustment and control Power via the HTML interface, sequential starting of the installation and optimisation of backup time by shutting down
◗Adjustment of date and time via NTP server - Daylight Saving Time management
◗Protection by encrypted password.
◗Protection by secured connection SSL and SSH
◗Saving of logs in the
◗Automatic language detection according to browser configuration.
◗Languages available: English / French / Spanish / German / Italian
◗
◗Card firmware updated via the network
◗Card configuration deployment on your installed base through network utility (Mupgrade)
1.7.3 Network
◗Fast ETHERNET 10/100 Mbits compatibility with
◗SNMP trap port modifiable (by default = 162)
1.7.4 MIB (Management Information Base)
◗MIB IETF UPS (RFC1628) for UPS
◗MIB MGE V1.7 AD, for UPS
◗MIB MGE V2.2 AA, for STS
1.7.5 Environment sensor
◗Temperature measurement from 0 to 70 °C with +/- 1° C accuracy
◗Measurement of humidity from 0 to 100 % with +/- 6 % accuracy
◗Min / max
◗Choice of temperature readings in Celsius or Fahrenheit
◗High and low thresholds, hysteresis and offset adjustable via Web interface
Network Management Card – User Manual | 34003676EN/HA | Page 9/81 |