Schneider Electric 66846, 66074 user manual Access is disabled and the card is accessible in SSH

Page 52

Network

Management Card

User Manual

Change Community Read-only:Text field limited to 31 characters. This field is only validated after clicking on “Save” . Default value “public”.

Current Community Read/Write is: Enables read and write SNMP access control (GET and SET). Default value “public”.

Change Community Read/Write: Text field limited to 31 characters. This field is only validated after clicking on “Save” . Default value “public”.

Change Trap Port Number: Numeric field limited to 65534. Enables forwarding of traps sent by the card to a port other than the port usually used for SNMP. Default value 162.

SSL Activation: When selected, access to Web interface is made in secure mode (https). Telnet

access is disabled and the card is accessible in SSH.

Connections with Network Shutdown Modules stay in standard mode (secure TCP)

SSL Security Implementation

SSL

￿version 3.0

Method

￿ TLS_RSA_WITH_RC4_128_MD5

Auth

￿ RSA

Key Exchange

￿ RSA

Encryption

￿ RC4_128

Digest

￿ MD5

SSH Security Implementation

SSH v1

 

Method

==> SSH_CIPHER_3DES

Encryption

==> Triple_DES in CBC mode

This change takes effect after a card reboot.

Authentication for all html pages : Login/password Authentication is required for all pages.

Network Management Card – User Manual

34003676EN/HA

Page 52/81

Image 52
Contents Network Management Card NMC Transverse Environment Sensor Network Management Card Configuration Configuration VIA Telnet Configuration VIA SSHMAINTENANCE72 Software Upgrade Appendices Tables of Alarms and EventsGlossary Introduction Connecting the UPS / STS to the NetworkNetwork Management Card MGE supervisor Enterprise Power Manager Protecting the computers / serversMonitoring the UPSs over the network Network Shutdown module only available for UPS, not for STSHow to connect UPS / network Setting up the protection, for UPS onlyConnection Presentation of the Network Management Cards NMCDirect sending of E-mail Presentation of the Environment Sensor solutionSending text messages SMS Technical data 10/81 Basic configuration InstallationEnvironment Sensor Supervision / Administration via a Web browser Optimising the performance of your browserUPS / STS UPS propertiesUPS zone general information on the UPS UPS status zone essential informationBattery status zone STS zone general information on the STS STS propertiesSTS status zone essential information About Sources status zoneOn-line help 18/81 UPS 3-Phase display Normal input measurementsBattery measurements By Pass measurementsSTS 3-Phase display UPS Control Source 2 input measurement23/81 UPS weekly schedule programming Shutdown parameters Important noteViewing the alarms Logs UPS MeasurementsSTS Measurements 29/81 UPS Event log STS Event log31/81 System log 33/81 UPS Email Notification NotificationNotified events Mail message configuration see next Recipient ListOther settings STS Email NotificationEmail Message Settings UPS Email Message SettingsSender SubjectSTS Email Message Settings Email Example Configuration User Name and password by default are MgeupsNetwork Settings 42/81 System 44/81 UPS Notified Applications 46/81 Central Shutdown Configuration STS Notified Applications 49/81 Access control 51/81 Access is disabled and the card is accessible in SSH Time Status Configuration Log CharacteristicsEnvironment Environment status 56/81 UPS Environment Settings UPS Environment SettingsSTS Environment Settings Humidity4 Log Set-up of the shutdown parameters Shutdown criteria managed by the Management CardShutdown when backup time is less than Specific set-up for long autonomy installation 30 mnShutdown duration Different server and UPS shutdown sequences 63/81 4 Off/On command Configuring a set of cards with Mupgrade Configuration in local modeChoice 1 Snmp agent configuration menu MgeupsChoice 3 Access control Choice 2 UPS / STS parametersChoice 4 Restore default configuration Choice 5 Reset the cardConfiguration via SSH Configuration via TelnetPuTTY SSH Client Program 70/81 71/81 Card firmware upgrade using Mupgrade Windows Software upgradeCard software upgrade via Tftp Unix and Windows Tables of alarms and events UPS Alarm tableSTS Alarm table English FrenchUPS event table UPS STS event table 77/81 System alarm table Glossary Subnet mask TelnetTrap Snmp