Schneider Electric 66846, 66074 user manual Set-up of the shutdown parameters

Page 60

Network

Management Card

User Manual

4 Servers protection, UPS only

4.1Set-up of the shutdown parameters

The Network Shutdown Module, on protected server boot, subscribes itself automatically to Notified

Applications list and sends its essential data:

IP address or name of the server on which it is installed, to be notified by the card of any power events

Time required to shutdown the server (Shutdown Duration, configurable in the Shutdown Module “set-up” menu):

The card takes into account the longest shutdown time of all the Network Shutdown Modules subscribed to manage UPS shutdown without affecting any of the servers protected.

In case of a major power event, the Shutdown Module receives messages from the card and regularly checks

its accessibility. The most important messages can generate actions and are sent back to the administrator and

users via the network.

When the server shuts down, the Shutdown Module unsubscribes itself from the Notified Applications.

4.1.1 Shutdown criteria managed by the Management Card

During an extended power failure, three criteria may cause the server shutdown procedure to be initiated. If several criteria are selected, the first criterion encountered will launch the shutdown procedure.

At the end of the shutdown procedure, when all servers have been shut down, the UPS may shut down to avoid unnecessary discharge of its batteries, depending on its configuration.

4.1.1.1 Backup time before initiating the shutdown procedure (Shutdown After)

When the UPS switches to battery, the Network Management Card starts the Shutdown Timer countdown and launches the system shutdown procedure at the end of the countdown.

This value must be chosen so that users have time to complete their tasks and disconnect, without exceeding battery backup time.

By default, this value is set to 30 minutes. Since GA release, this criterion is not selected in the default configuration

Note 1:

The Network Shutdown Module can also manages its own Shutdown Timer (configurable in the Shutdown Module “set-up” menu)

Note that if this criterion is selected to initiate system shutdown, automatic system reboot when power is restored is not guaranteed (e.g. power restoration if only this system was shut down).

By default, this parameter is not selected.

4.1.1.2 Initiating the shutdown procedure when the battery level is lower than: (if capacity under)

When the card detects that the remaining backup time percentage is less than the configured level, the shutdown sequence is started.

By default, the card uses the value set in the UPS.

Note:

Certain types of UPS only accept pre-defined minimum battery level values. Check the UPS documentation.

Network Management Card – User Manual

34003676EN/HA

Page 60/81

Image 60
Contents Network Management Card NMC Transverse Environment Sensor Network Management Card Configuration Configuration VIA Telnet Configuration VIA SSHMAINTENANCE72 Software Upgrade Appendices Tables of Alarms and EventsGlossary Connecting the UPS / STS to the Network IntroductionNetwork Management Card MGE supervisor Enterprise Power Manager Protecting the computers / serversMonitoring the UPSs over the network Network Shutdown module only available for UPS, not for STSHow to connect UPS / network Setting up the protection, for UPS onlyConnection Presentation of the Network Management Cards NMCPresentation of the Environment Sensor solution Direct sending of E-mailSending text messages SMS Technical data 10/81 Installation Basic configurationEnvironment Sensor Supervision / Administration via a Web browser Optimising the performance of your browserUPS / STS UPS propertiesUPS zone general information on the UPS UPS status zone essential informationBattery status zone STS properties STS zone general information on the STSSTS status zone essential information About Sources status zoneOn-line help 18/81 UPS 3-Phase display Normal input measurementsBattery measurements By Pass measurementsSTS 3-Phase display UPS Control Source 2 input measurement23/81 UPS weekly schedule programming Shutdown parameters Important noteViewing the alarms Logs UPS MeasurementsSTS Measurements 29/81 UPS Event log STS Event log31/81 System log 33/81 Notification UPS Email NotificationNotified events Mail message configuration see next Recipient ListOther settings STS Email NotificationEmail Message Settings UPS Email Message SettingsSender SubjectSTS Email Message Settings Email Example Configuration User Name and password by default are MgeupsNetwork Settings 42/81 System 44/81 UPS Notified Applications 46/81 Central Shutdown Configuration STS Notified Applications 49/81 Access control 51/81 Access is disabled and the card is accessible in SSH Time Characteristics Status Configuration LogEnvironment Environment status 56/81 UPS Environment Settings UPS Environment SettingsSTS Environment Settings Humidity4 Log Set-up of the shutdown parameters Shutdown criteria managed by the Management CardSpecific set-up for long autonomy installation 30 mn Shutdown when backup time is less thanShutdown duration Different server and UPS shutdown sequences 63/81 4 Off/On command Configuring a set of cards with Mupgrade Configuration in local modeChoice 1 Snmp agent configuration menu MgeupsChoice 3 Access control Choice 2 UPS / STS parametersChoice 4 Restore default configuration Choice 5 Reset the cardConfiguration via Telnet Configuration via SSHPuTTY SSH Client Program 70/81 71/81 Software upgrade Card firmware upgrade using Mupgrade WindowsCard software upgrade via Tftp Unix and Windows Tables of alarms and events UPS Alarm tableSTS Alarm table English FrenchUPS event table UPS STS event table 77/81 System alarm table Glossary Subnet mask TelnetTrap Snmp
Related manuals
Manual 18 pages 57.58 Kb