5-4
ADA M 4000 Series User’s Manual
4011, 4011D, 4012, 4013, 4015, 4015T, 4016,
4017, 4017+, 4018, 4018+, 4018M, 4019+
%AANNTTCCFF
Name Configuration command
Description Sets address, input range, baud rate, data format, checksum
status, and/or integration time for an analog input module.
Syntax %AANNTTCCFF(cr)
% is a delimiter character.
AA (range 00-FF) represents the 2-character hexadecimal
address of the analog input module you want to configure.
NN represents the new hexadecimal address of the analog
input module. Range is from 00h to FFh.
TT represents the type (input range) code. (Note: 4015 and
4019 must be 00)
(Refer to Table 5-1 on Page 5-6)
CC represents the baud rate code.
(Refer to Table 5-2 on Page 5-8)
FF is a hexadecimal number that equals the 8-bit parameter
representing the data format, checksum status and
integration time. The layout of the 8-bit parameter is shown
in Figure 5-1. Bits 2 through 5 are not used and are set to 0.
(cr) is the terminating character, carriage return (0Dh)
76543210
Checksum status
0: Dis abled
1: En able d
Integration tim e
0: 50 ms (Ope ration under 60 Hz po wer)
1: 60 ms (Ope ration unde r 50 Hz powe r)
not used
00: Engineeri ng uni ts
01 : % of FSR
10: two's complement of hexadecimal
1 1: Ohms (for 4013 an d 4015)
Data Format
Figure 5-1 Data format for FF (8-bit parameter)