Command Set
4-
22
ADAM 4000 Series User’s Manual

ADAM-4019+ Command Table

Command Syntax Command Name Command Description Page
No.
%AANNTTCCFF Configuration Sets the address, baud rate, data
format, checksum status, and/or
integration time for a specified
analo
g
input module
5-4
$AA2 Configuration
Status Returns the configuration
parameters for the specified
analo
g
input module
5-10
$AAF Read Firmware
Version Return the firmware version code
from the specified analog output
module
5-12
$AAM Read Module
Name Return the module name from the
specified analog output module 5-13
#AA Analog Data In Returns the input value from a
specified analog input module in
the currently configured data
format
5-14
#AAN Read Analog Input
from Channel N Returns the input value from a
specified channel of analog input
module in the currently configured
data format
5-16
$AA5VV Enable/Disable
Channels for
Multiplexing
Enable or disable the individual
channels in an analog module 5-17
$AA6 Read Channel
Status
Get the enable/disable status of all
channels in an analo
g
module
5-18
$AAB Get Operating Status Get the channel operating status
When
bit value is 0, it mean t his cha n nel i s in
norm al o p er ating, w hen bit valu e is 1, it
mean this channel is opening wire
5-24
$AA3 CJC Status Returns the value of the CJC
sensor for a specified analog input
module
5-25
$AA9SNNNN CJC Offset
Calibration Calibrates an analog input module to
adjust for offset errors of its CJC
sensors
5-26

(Continued on following page)