Data Formats and I/O Ranges
B-
8
ADAM 4000 Series User’s Manual
Range
Code
(hex)
Input Range
Description Data Formats
Maximum
Specified
Signal
Minimum
Specified
Signal
Displayed
Resolution
0F
Type K
Thermocouple
0°C to 1370°C
Engineering
Units +1370.0 +0000.0 0.1°C
% of FSR +100.00 +000.00 0.01%
Twos
Complement 7FFF 0000 1 LSB*
10
Type T
Thermocouple
-100°C to 400°C
Engineering
Units +400.00 -100.00 0.01°C
% of FSR +100.00 -0.25.00 0.01%
Twos
Complement 7FFF E000 1 LSB*
11
Type E
Thermocouple
0°C to 1000°C
Engineering
Units +1000.0 +0000.0 0.1°C
% of FSR +100.00 +000.00 0.01%
Twos
Complement 7FFF 0000 1 LSB*
12
Type R
Thermocouple
500°C to 1750°C
Engineering
Units +1750.0 +0500.0 0.1°C
% of FSR +100.00 +028.57 0.01%
Twos
Complement 7FFF 2492 1 LSB*
13
Type S
Thermocouple
500°C to 1750°C
Engineering
Units +1750.0 +0500.0 0.1°C
% of FSR +100.00 +028.57 0.01%
Twos
Complement 7FFF 2492 1 LSB*
14
Type B
Thermocouple
500°C to 1800°C
Engineering
Units +1800.0 +0500.0 0.1°C
% of FSR +100.00 +027.77 0.01%
Twos
Complement 7FFF 2381 1 LSB*
20
100.00 Ω
Platinum RTD
α = .00385
-100°C to 100°C
Engineering
Units +100.00 -100.000 0.1°C
% of FSR +100.00 +000.00 0.01%
Twos
Complement 7FFF 8000 1 LSB*
Ohms +138.50 +060.60 10 m
21
100.00
Platinum RTD
α = .00385
0°C to 100°C
Engineering
Units +100.000 +000.00 0.1°C
% of FSR +100.00 +000.00 0.01%
Twos
Complement 7FFF 0000 1 LSB*
Ohms +138.50 +100.00 10 m