Command Set
4-
28
ADAM 4000 Series User’s Manual

ADAM-4051 Command Table

Command Syntax Command Name Command Description Page
No.
%AANNTTCCFF Configuration Sets the address, baud rate, and/or
checksum status to a digital I/O
module
7-4
#** Synchronized
Sampling Orders all digital I/O modules to
sample their input values and store
them in special re
g
isters
7-11
$AA2 Configuration
Status Returns the configuration
parameters of a specified dig ita l I/ O
module
7-14
$AA4 Read
Synchronized Data
Returns the value of a specified
digital I/O module that was stored in
the specified register after an #**
command was issu ed
7-12
$AA5 Reset Status Indicates whether a specified digital
I/O module was reset after the last
time that $AA5 command was
issued
7-16
$AA6 Digital Data In Returns the values of the digital I/O
channel in the addressed module 7-6
$AAF Read Firmware
Version Return the firmware version code
from the specified digital I/O module 7-18
$AAM Read Module
Name Return the module name from the
specified di
g
ital I/O module
7-19