Installation Guideline
2-
8
ADAM 4000 Series User’s Manual
Module at address 01 responds that it is configured for an input
range of +/-2.5 V, baud rate of 9600, integration time of 50 ms (60 Hz).
The code also shows engineering units and no checksum checking or
generation.
To change the configuration setting of the analog input module, the
following command is issued:
%01070F0600(cr)
% = change configuration
01 = target module at address 00 to:
07 = change address to 07 hexadecimal
0F = set input range to Type K thermocouple
06 = set baud rate to 9600
00 = set integration time to 50 ms (60 Hz)
disable checksum
set data format to engineering units
(Please refer to Chapter 4, a full description of Command set syntax for
an analog input module)
When the module received the configuration command, it will
respond with its new address as shown below:
!07(cr)
Before giving more commands to the module, please wait for 7
seconds to let the new configuration settings to take effect.
NOTICE: All reconfiguration except for changing baud rate and
checksum values can be done dynamically, and the modules are not
required to reset. However, all the connected devices are required to
reset by turning power off and on after the baud rate or checksum
values are changed. The baud rate or checksum values should be the
same for all the connected devices after the reconfiguration. See the
next page for a strategy in changing baud rate and checksum of the
network.