Installation Guideline
2-
10
ADAM 4000 Series User’s Manual
• Power on all components except the ADAM Module.
Power the ADAM module on while shorting the INIT* and GND
terminals (See Figure 2-3) or set the INIT switch to “Init” (See
Figure 2-4)
Figure 2-3 G rou nding the INIT* Terminal
Figure 2-4 Set INIT switch to “Init”
• Configure the checksum status and/or the baud rate.
• Switch the power OFF to the ADAM Module.
Remove the grounding of the INIT* terminal and turn on the
module, or set the INIT switch to “Normal”.
Check the settings (If the baud rate has changed, the settings on the
host computer should be changed accordingly).