Command Set
4-
18
ADAM 4000 Series User’s Manual

ADAM-4018+ Command Table

Command Syntax Command Name Command Description Page No.
%AANNTTCCFF Configuration Set the address, input range, baud
rate, data format, checksum status
and/or integration time for the
specified analo
g
input module
5-4
$AA2 Configuration Status Return the configuration
parameters for the specified analog
input module
5-10
$AAF Read Version Return the firmware version code
from the specified analog input
module
5-12
$AAM Read Module Name Return the module name from the
specified analo
g
input module
5-13
#AA Read Analog Input
from all Channels Return the input value from all
channels of the specified analog
module
5-14
#AAN Read Analog Input
from Channel N Return the input value from
channels number N of the
specified analo
g
input module
5-16
$AA5VV Enable/disable
Channels for
Multiplexing
Enables/disa ble s multiplexing
simultaneously for seperate
channels of the specified input
module
5-17
$AA6 Read Channel
Status Ask the specified input module to
return the status of all eight
channels
5-18
$AAB Get Operating Status
Get the channel operating status When
bit value is 0, it mean t his cha n nel i s in
norm al operat i ng , w h e n bit value is 1, it
mean this channel is opening wire
5-24
$AA3 CJC Status Returns the value of the CJC
sensor for a specified an alo g input
module
5-25
$AA9SNNNN
CJC Offset
Calibration Calibrates an analog input module to
adjust for offset errors of its CJC
sensors
5-26
$AA0Ci Span Calibration
Gai n er ror c al i brate of assignm en t
channel, User have to input the external
standard source for calibrating process
5-27

(Continued on following page)