Analog Output Module Command Set
6-
10
ADAM 4000 Series User’s Manual
$AA3
Example command: $07314(cr)
response: !07(cr)
The command tells the analog output module at address
07h to increase its output value by 20 (14h) counts which
are approximately 30 μA.
The analog output module confirms the increase.
In order to perform this trim calibration, a millimeter or a
resistor and voltmeter should be connected to the module’s
output. (Please see the 4 mA Calibration command and 20
mA Calibration command of the analog output module’s
command set. Please also refer to Chapter 8, Calibration
for a detailed description.)
4021