Command Set
4-
8
ADAM 4000 Series User’s Manual

ADAM-4012 Command Table

Command S
y
ntax
Command Name
Command Description
Pa
g
e No.
%AANNTTCCFF Configuration Sets the address, input range,baud
rate, data format, checksum
status, and/or integration time for a
specified analo
g
input module
5-4
#AA Analog Data In Returns the input value from a
specified analog input module in
the currently configured data
format
5-14
$AA0 Span Calibration Calibrates an analog input module
to correct for
g
ain errors
5-19
$AA1 Offset Calibration Calibrates an analog input module
to correct for offset errors 5-20
#** Synchronized
Sampling Orders all analog input modules to
sample their input values and store
them in special re
g
isters
5-21
$AA4 Read Synchronized
Data Returns the value that was stored
in the specified module's register
after the #** command
5-22
$AA2 Configuration Status Returns the configuration
parameters for the specified
analog input module
5-10
$AAF Read Firmware
Version Return the firmware version code
from the specified analog input
module
5-12
$AAM Read Module Name Return the module name from the
specified analog input module 5-13
(Continued on following page)