Command Set
4-
12
ADAM 4000 Series User’s Manual

ADAM-4016 Command Table

Command Syntax
Command Name Command Description Page No.
%AANNTTCCFF Configuration Set the address, input range, baud
rate, data format, checksum status
and/or integration time for the
specified analo
g
input module
5-4
$AA2 Configuration Status Return the configuration
parameters for the specified
analo
g
input module
5-10
$AAF Read Firmware
Version Return the firmware version code
from the specified analog input
module
5-12
$AAM Read Module Name Return the module name from the
specified analo
g
input module
5-13
#AA Read Analog Input Return the input value from the
specified analog input module in
the currently configured data
format
5-14
$AA0 Span Calibration Calibrate an analog input module
to correct for
g
ain errors
5-19
$AA1 Offset Calibration Calibrate an analog input module
to correct for offset errors
5-20
#** Synchronized
Sampling Orders all analog input modules to
sample their input values and store
them in special registers
5-21
$AA4 Read Synchronized
Data Returns the value that was stored
in the specified module's register
after the #** command
5-22
$AA6 Get Excitation
Voltage Output Value Returns either last value sent to
specified module by $AA7
command, or start-up output
voltage
5-65
$AA7 Excitation Voltage
Output
Direct output excitation voltage
data to a specified module
5-66
$AAS Start-up Voltage
Output Configuration
Stores a default value in a
specified module. The output value
will take effect upon atartup.
5-67
$AAE Trim Calibration Trims specified module a number
of units up or down 5-69
$AAA Zero Calibration Tells the module to store
paramenters for zero calibration 5-70
$AAB Span Calibration Tells the module to store
parameters for span calibration 5-71
(Continued on following page)