Chapter 5
5-7
ADAM 4000 Series User’s Manual
4011, 4011D, 4012, 4013, 4015, 4015T, 4016,
4017, 4017+, 4018, 4018+, 4018M, 4019+
Input Range Code (Hex) Input Range for 4013
20 Platinum, -100 ~ 100 , a=0.00385
21 Platinum, 0 ~ 100 , a=0.00385
22 Platinum, 0 ~ 200 , a=0.00385
23 Platinum, 0 ~ 600 , a=0.00385
24 Platinum, -100 ~ 100 , a=0.003916
25 Platinum, 0 ~ 100 , a=0.003916
26 Platinum, 0 ~ 200 , a=0.003916
27 Platinum, 0 ~ 600 , a=0.003916
28 Nickel, -80 ~ 100
29 Nickel, 0 ~ 100
ADAM-4015/4015T command codes against Input ranges table
Command Code (Hex) Input Type Input Range
20 Platinum 100 (IEC) -50 ~ 150
21 Platinum 100 (IEC) 0 ~ 100
22 Platinum 100 (IEC) 0 ~ 200
23 Platinum 100 (IEC) 0 ~ 400
24 Platinum 100 (IEC) -200 ~ 200
25 Platinum 100 (JIS) -50 ~ 150
26 Platinum 100 (JIS) 0 ~ 100
27 Platinum 100 (JIS) 0 ~ 200
28 Platinum 100 (JIS) 0 ~ 400
29 Platinum 100 (JIS) -200 ~ 200
2A Platinum 1000
-40 ~ 160
2B BALCO 500
-30 ~ 120
2C Ni 604 -80 ~ 100
2D Ni 604 0 ~ 100
IEC RTD 100O , α = 0.00385
JIS RTD 100O, α = 0.00391