Digital I/O and Relay Output
Counter/Frequency Command Set
7-
10
ADAM 4000 Series User’s Manual
#AABB
Examples command: #140005(cr)
response: >(cr)
An output byte with value 05h (00000101) is sent to the
digital I/O module at address 14h (Either ADAM-4050 or
ADAM-4060). Its channel 0 and 2 will be set to ON.
Other channels are set to OFF.
command: #151201(cr)
response: >(cr)
An output bit with value 1 is sent to channel 2 at address
15h of a digital I/O module (Either ADAM-4050 or
ADAM-4060).
Channel 2 of the digital I/O module is set to ON.
command: #1400017A(cr)
response: >(cr)
An output byte with value 017Ah (0000000101111010) is
sent to the digital I/O module at address 14h (Either
ADAM-4056S or ADAM-4056SO). Its channel 1, 3, 4, 5, 6,
and 8 will be set to ON. Other channels are set to OFF.
command: #15120001(cr)
response: >(cr)
An output bit with value 1 is sent to channel 2 of a digital
I/O module at address 15h (Either ADAM-4056S or
ADAM-4056SO). Channel two of the digital I/O module is
set to ON.
4050, 4055, 4056S,
4056SO, 4060, 4068, 4069