Chapter 4

Chapter 4 Command Set
4-19
ADAM-4018+ Command Table (Continued)
Command S
y
ntax
Command Name
Command Description
Pa
g
e No.
$AA1Ci Offset Calibration
Offset error calibrate of ass ignment
channel, User have to input the external
standard source for calibrating process
5-28
$AA7CiRrr Input Ran
g
e Settin
g
Input range setting individually 5-29
$AA8Ci Read Input Range Get the input range
of t he ass ignment
channel 5-30
$AAXnnnn Set Communication
WDT Set communication WDT cycle time from
0000 ~ 9999 (unit: 0.1 second. if value is
0000, the communic ation WDT function
will be disable)
5-31
$AAY Get Communication
WDT Settin
g
Read the cycle time setting of
communication WDT 5-32

ADAM-4018+

Input range and external calibrating input source for each input type

Range
bcode(Hex) Input Range Max. Signal Min Signal Displayed
Resolution
06 +/-20 mA
+20.000
-20.000
1uA
07 4~20 mA +20.000 +4.000 1uA
14 Type J
Thermocouple
15 Type K
Thermocouple
16 Type T
Thermocouple
17 Type E
Thermocouple
18 Type R
Thermocouple
19 Type S
Thermocouple
20 Type B
Thermocouple