Chapter 6
6-
7
ADAM 4000 Series User’s Manual
#AA
Example command: #3315.000(cr)
response: >(cr)
The command sends the value 15 mA, which is converted
to engineering units, to the address 33h of the analog output
module. The analog output module responds with an output
value of 15 mA which represents a valid command.
command: #0A+030.00(cr)
response: >(cr)
The module is configured for an output range of 4 to 20 mA
and a percent of span data format. The command sends the
value 8.8 mA (4 mA + 0.30 x 16 mA = 8.8 mA) which is
30% of the span to the address 0Ah of analog output
module. The analog output module responds with an output
value of 8.8 mA which represents a valid command.
command: #1B7FF(cr)
response: >(cr)
The command sends the hexadecimal value 7FF to the
analog output module at address 1Bh. The module is
configured to a 0 to 20 mA output range and a hexadecimal
data format. It will output with a value of 10 mA
((7FFH/FFFH) x 20 mA = 10 mA).
4021