Technical Specifications
A-
20
ADAM 4000 Series User’s Manual
Table A-12 ADAM-4018M Range Accuracy for Thermocouple
Input
Range
Code
(Hex)
Input Range Typical
Accuracy
Maximum
Error Units
0E J thermocouple
0 to 760 ℃ ±1.0 ±1.5 ℃
0F K thermocouple
0 to 1370 ℃ ±1.0 ±1.5 ℃
10 T thermocouple
-100 to 400 ℃ ±1.0 ±1.5 ℃
11 E thermocouple
0 to 1000 ℃ ±1.0 ±1.5 ℃
12 R thermocouple
500 to 1750 ℃ ±1.2 ±2.5 ℃
13 S thermocouple
500 to 1750 ℃ ±1.2 ±2.5 ℃
14 B thermocouple
500 to 1800 ℃ ±2.0 ±3.0 ℃
NOTE: Because the CJC sensor of ADAM-4018M is located in
the side of channel 0 to 4, the measurement will have the
difference ± 1 ℃ between channel 0 ~ 4 and channel 5 ~ 7.