Technical Specifications
A-
20
ADAM 4000 Series User’s Manual
Table A-12 ADAM-4018M Range Accuracy for Thermocouple
Input
Range
Code
(Hex)
Input Range Typical
Accuracy
Maximum
Error Units
0E J thermocouple
0 to 760 ±1.0 ±1.5
0F K thermocouple
0 to 1370 ±1.0 ±1.5
10 T thermocouple
-100 to 400 ±1.0 ±1.5
11 E thermocouple
0 to 1000 ±1.0 ±1.5
12 R thermocouple
500 to 1750 ±1.2 ±2.5
13 S thermocouple
500 to 1750 ±1.2 ±2.5
14 B thermocouple
500 to 1800 ±2.0 ±3.0
NOTE: Because the CJC sensor of ADAM-4018M is located in
the side of channel 0 to 4, the measurement will have the
difference ± 1 between channel 0 ~ 4 and channel 5 ~ 7.