Command Set
4-
6
ADAM 4000 Series User’s Manual

ADAM- 4011D Comm and Table

Command S
y
ntax
Command Name
Command Description
Pa
g
e No.
%AANNTTCCFF Configuration Sets the address, input range,baud
rate, data format, checksum
status, and/or integration time for a
specified analog input module
5-4
$AA2 Configuration Status Returns the configuration
parameters for the specified
analo
g
input module
5-10
$AAF Read Firmware
Version Return the firmware version code
from the specified analog input
module
5-12
$AAM Read Module Name Return the module name from the
specified analo
g
input module
5-13
#AA Analog Data In Returns the input value from a
specified analog input module in
the currently configured data
format
5-14
$AA0 Span Calibration Calibrates an analog input module
to correct for gain errors 5-19
$AA1 Offset Calibration Calibrates an analog input module
to correct for offset errors
5-20
#** Synchronized
Sampling Orders all analog input modules to
sample their input values and store
them in special re
g
isters
5-21
$AA4 Read Synchronized
Data Returns the value that was stored
in the specified module's register
after the #** command
5-22
$AAB Open Thermocouple
Detection Ask the module to respond
whether the thermocouple is open
or not
5-24
$AA3 CJC Status Returns the value of the CJC
sensor for a specified an alo g i npu t
module
5-25
$AA9SNNNN CJC Offset
Calibration
Calibrates the CJC sensor for
offset errors
5-26

(Continued on following page)