Chapter 6

6-
21
ADAM 4000 Series User’s Manual

ADAM-4024 Command Review: (Continued)

Command Set Function
Response
Example
$AA8Cn Read Back CHn Output Range
!AACnxx
$027C2
$AAACnZ Enable/Disable (Z=1/0) CHn EMS Flag
!AA
$02AC21
$02AC20
$AABCn Read CHn EMS Flag !AACn1
!AACn0
$02BC2
$AADCn Read Back CHn StartUp Data !AA(data)
$02DC2
$AAECn Read Back CHn Emergency Stop Data
!AA(data)
$02EC2
$AAF Read Firmware Version
!AAAx.xx
$02F
$AAG Reset Current Trim Data Variable To 0
!AA
$02G
$AAH Read Current Trim Data Variable !AAxx (xx=m)
$02H
$AAI Read IDI !AAx $02I
$AAM Read Module Name !AA4024 $02M
$AANCn Read Back CHn 4mA Calibration
Parameter
!AAxx $02NC2
$AAOCn Read Back CHn 20mA Calibration
Parameter
!AAxx
$02OC2
$AAPCn Clear CHn 4mA Calibration Parameter /
EEPROM
!AA
$02PC2
$AAQCn Clear CHn 20mA Calibration Parameter /
EEPROM
!AA
$02QC2
$AAXnnnn This command set the communication
watchdog timer (WDT) cycle time.
AA: (range 00-FF) 2-character
hexadecimal address of the analog input
module which is to be read.
X: the setting WDT command.
Nnnn: (range 0000~9999) the specified
value of communication cycle you want to
set. (Unit: 0.1 second)
!AA $02X1234
$AAY Read Communication Watchdog Timer
Cycle Setting.
AA: (range 00-FF) 2-character
hexadecimal address of the analog input
module which is to be read.
Y: the reading WDT cycle command.
!AA
$02Y

4024