ADAM 4000 Series User’s Manual
#**
Name Synchronized Sampling command
Description Orders all (analog or digital) input modules to sample their
input values and store them into a special register.
Syntax #**
# is a delimiter character.
** is the Synchronized Sampling command.
The terminating character, in the form of a carriage
return (0Dh), is not required.
Response The digital I/O modules will not respond to the
Synchronized Sampling command. In order to retrieve the
data, you must execute a Read Synchronized Data
command for every module separately.
4050, 40 51, 4052, 4053,
4055, 4060, 4068,