Operation

Alarm Messages

The alarm message area displays the alarm conditions that are present within the UPS system. The table below shows the default values of masks for each alarm/fault, the meaning of the Alarm and possible corrective actions.

The following information applies to the table.

1.Latch Masks, Dial Masks and unshaded Event log masks may be changed by the user. The user may not change any Freeze Masks.

2.The default alarm names for Input Contact 1 through Input Contact 8 can be modified by the user.

Table 7

Alarms, functions, and corrective actions

 

 

 

 

 

 

 

 

 

 

 

Actual

 

 

 

 

 

 

 

 

Alarm/fault

 

 

 

 

 

 

 

 

Name

 

Description

Fault

 

 

 

 

 

Displayed

 

 

 

 

 

 

On Front

 

of Alarm/

Or

Latch

Dial

Freeze

Event Log

 

Panel

 

Fault

Alarm

Mask

Mask

Mask

Mask

Meaning and Corrective Action(s)

 

 

 

 

 

 

 

 

Control Logic has determined that the

 

 

 

 

 

 

 

 

battery breaker(s) is closed and the battery

Battery Fuse

 

Battery Fuse

Fault

YES

YES

NO

YES

fuse has been open for 10 seconds or

Fail

 

Fail

longer. Battery back-up is no longer

 

 

 

 

 

 

 

 

 

 

 

 

 

 

available. Liebert Global Services should

 

 

 

 

 

 

 

 

be called immediately.

 

 

 

 

 

 

 

 

Control Logic has determined that the

 

 

 

 

 

 

 

 

battery breaker(s) is closed and the battery

 

 

 

 

 

 

 

 

voltage has dropped below the End of

 

 

 

 

 

 

 

 

Discharge limit. The UPS will transfer to

 

 

 

 

 

 

 

 

bypass. If the transfer is successful, the

Battery Low

 

Battery Low

 

 

 

 

 

UPS will be shut down. If the transfer was

 

Fault

YES

YES

YES

YES

unsuccessful, logic will attempt to complete

xfer

 

Transfer

 

 

 

 

 

 

a System Shutdown before control power is

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

lost. Verify that input power is now available

 

 

 

 

 

 

 

 

and restart the UPS following the

 

 

 

 

 

 

 

 

instructions in this manual. If the system

 

 

 

 

 

 

 

 

fails to restart properly contact Liebert

 

 

 

 

 

 

 

 

Global Services.

 

 

 

 

 

 

 

 

DC bus voltage is 15% or more over the

DC Ov

 

DC Overvolt

 

 

 

 

 

nominal DC Bus Voltage. The UPS will

 

Fault

YES

YES

NO

YES

transfer the load to Bypass and will shut

Transient

 

Transient

 

 

 

 

 

 

down and isolate the UPS Module. Contact

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Liebert Global Services immediately

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The power conductors on the Input line are

 

 

 

 

 

 

 

 

not wired to the UPS in the required

 

 

 

 

 

 

 

 

sequence. This alarm should appear only

Inp Phase

 

Input Phase

Fault

NO

NO

NO

YES

during initial start-up or after a repair to the

Rot Error

 

Rotation Error

source power system. Disconnect power

 

 

 

 

 

 

 

 

 

 

 

 

 

 

from the Input line and correct the wiring.

 

 

 

 

 

 

 

 

Liebert Global Services must be present

 

 

 

 

 

 

 

 

during initial start-up of your UPS System.

 

 

 

 

 

 

 

 

At least one fuse has opened. The UPS

 

 

 

 

 

 

 

 

automatically transfers the critical load to

Rectifier Fuse

Rectifier Fuse

 

 

 

 

 

the bypass line. Contactors trip open to

Fault

YES

YES

NO

YES

shut down and isolate the UPS module.

Fail

 

Fail

 

 

 

 

 

 

Contact Liebert Global Services

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

immediately. Do not attempt to reset the

 

 

 

 

 

 

 

 

circuit breakers.

74

Page 82
Image 82