Operation

Automatic Module Off Line

For specified UPS system faults, the control logic will initiate an automatic transfer to bypass fol- lowed immediately by a shutdown and isolation of the UPS system. All UPS contactors and the bat- tery circuit breaker are opened. The static bypass switch will close if the bypass line is available. Note that the bypass line is usually not available during Low Battery Shutdown.

The following UPS system faults will initiate an automatic transfer to bypass:

DC Over-Voltage Shutdown

Hardware Shutdown

Inverter Fault

Low-Battery Shutdown

Output Over-Voltage

Overload Shutdown

Over-Temperature Time out

Rectifier Fuse Blown

Reverse Power

Refer to 3.4 - Faults, Alarms, Status for more information regarding these alarm messages.