Operation

Table 7

Alarms, functions, and corrective actions (continued)

 

 

 

 

 

 

 

 

 

 

Actual

 

 

 

 

 

 

 

 

Alarm/fault

 

 

 

 

 

 

 

 

Name

 

 

 

 

 

 

 

 

Displayed

 

Description

Fault

 

 

 

 

 

On Front

 

of Alarm/

Or

Latch

Dial

Freeze

Event Log

 

Panel

 

Fault

Alarm

Mask

Mask

Mask

Mask

Meaning and Corrective Action(s)

 

 

 

 

 

 

 

 

The maximum heat sink temperature limit

 

 

 

 

 

 

 

 

has been exceeded. (Should be preceded

 

 

 

 

 

 

 

 

by a “Heatsink” Overtemp Warning alarm).

 

 

 

 

 

 

 

 

The load will be transferred to the Static

 

 

 

 

 

 

 

 

Bypass if available. If the load was already

 

 

 

 

 

 

 

 

on SBS when this alarm occurred, the

Hsink ovtemp

Heatsink

 

 

 

 

 

system will shut down. The fault will clear

Overtemp

Fault

YES

YES

YES

YES

when the temperature falls below the

limit

 

 

Limit

 

 

 

 

 

Heatsink Overtemp Warning threshold. (If

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

this fault doesn’t clear soon enough it will

 

 

 

 

 

 

 

 

lead to an “Overtemp Time-out Shutdown”).

 

 

 

 

 

 

 

 

If the unit is still running it will make an

 

 

 

 

 

 

 

 

attempt to auto-retransfer when the fault

 

 

 

 

 

 

 

 

clears. If the faults do not clear; contact

 

 

 

 

 

 

 

 

Liebert Global Services.

 

 

 

 

 

 

 

 

The input source is present, but the input

Inp pwr

 

Input Power

 

 

 

 

 

power supply has failed. The unit has

 

Fault

NO

YES

NO

YES

redundant power supplies on both the input

supply fail

 

Supply Fail

 

 

 

 

 

 

and the output. Contact Liebert Global

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Services immediately.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The output source is present, but the output

Out pwr

 

Output Power

 

 

 

 

 

power supply has failed. The unit has

 

Fault

NO

YES

NO

YES

redundant power supplies on both the input

supply fail

 

Supply Fail

 

 

 

 

 

 

and the output. Contact Liebert Global

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Services immediately.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The Outlet air temperature has exceeded

 

 

 

 

 

 

 

 

its maximum set point. The UPS will

 

 

 

 

 

 

 

 

transfer the load to bypass if available. If

 

 

 

 

 

 

 

 

already on bypass the system will

 

 

 

 

 

 

 

 

shutdown. The fault will clear when the

 

 

 

 

 

 

 

 

temperature falls below the Outlet Air

 

 

 

 

 

 

 

 

Overtemp Warning threshold. (If this fault

Ups Ambient

 

UPS Ambient

Fault

YES

YES

YES

YES

doesn’t clear soon enough it will lead to an

Limit

 

Ot Limit

“overtemp Time-out Shutdown”.). If the unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

is still running when the fault clears it will

 

 

 

 

 

 

 

 

auto retransfer to UPS. Check all air inlets

 

 

 

 

 

 

 

 

and exhausts for blockage and check the

 

 

 

 

 

 

 

 

air filter. Check the actual load against the

 

 

 

 

 

 

 

 

UPS rating. Remove any excess load.

 

 

 

 

 

 

 

 

Contact Liebert Global Services if the alarm

 

 

 

 

 

 

 

 

persists.

 

 

 

 

 

 

 

 

Failure of this fuse will remove control

 

 

 

 

 

 

 

 

power. The UPS will attempt to transfer to

Pwr Supply

 

Power Supply

Fault

NO

YES

NO

YES

Static Bypass if available. Locate the cause

F1 Fail

 

F1 Fail

of any failure, before replacing a fuse or

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Contact Liebert Global Services

 

 

 

 

 

 

 

 

Immediately.

 

 

 

 

 

 

 

 

UPS will transfer to Static Bypass if

SWGR Power

SWGR Power

Fault

NO

YES

NO

YES

available and shut down the UPS. Start-up

Fail

 

Fail

will be inhibited. Contact Liebert Global

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Services.

 

 

 

 

 

 

 

 

 