Operation
Table 7 | Alarms, functions, and corrective actions (continued) |
| |||||||
|
|
|
|
|
|
|
|
| |
Actual |
|
|
|
|
|
|
|
| |
Alarm/fault |
|
|
|
|
|
|
|
| |
Name |
|
|
|
|
|
|
|
| |
Displayed |
| Description | Fault |
|
|
|
|
| |
On Front |
| of Alarm/ | Or | Latch | Dial | Freeze | Event Log |
| |
Panel |
| Fault | Alarm | Mask | Mask | Mask | Mask | Meaning and Corrective Action(s) | |
|
|
|
|
|
|
|
| The maximum heat sink temperature limit | |
|
|
|
|
|
|
|
| has been exceeded. (Should be preceded | |
|
|
|
|
|
|
|
| by a “Heatsink” Overtemp Warning alarm). | |
|
|
|
|
|
|
|
| The load will be transferred to the Static | |
|
|
|
|
|
|
|
| Bypass if available. If the load was already | |
|
|
|
|
|
|
|
| on SBS when this alarm occurred, the | |
Hsink ovtemp | Heatsink |
|
|
|
|
| system will shut down. The fault will clear | ||
Overtemp | Fault | YES | YES | YES | YES | when the temperature falls below the | |||
limit |
| ||||||||
| Limit |
|
|
|
|
| Heatsink Overtemp Warning threshold. (If | ||
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
| this fault doesn’t clear soon enough it will | |
|
|
|
|
|
|
|
| lead to an “Overtemp | |
|
|
|
|
|
|
|
| If the unit is still running it will make an | |
|
|
|
|
|
|
|
| attempt to | |
|
|
|
|
|
|
|
| clears. If the faults do not clear; contact | |
|
|
|
|
|
|
|
| Liebert Global Services. | |
|
|
|
|
|
|
|
| The input source is present, but the input | |
Inp pwr |
| Input Power |
|
|
|
|
| power supply has failed. The unit has | |
| Fault | NO | YES | NO | YES | redundant power supplies on both the input | |||
supply fail |
| Supply Fail | |||||||
|
|
|
|
|
| and the output. Contact Liebert Global | |||
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| Services immediately. | |
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| The output source is present, but the output | |
Out pwr |
| Output Power |
|
|
|
|
| power supply has failed. The unit has | |
| Fault | NO | YES | NO | YES | redundant power supplies on both the input | |||
supply fail |
| Supply Fail | |||||||
|
|
|
|
|
| and the output. Contact Liebert Global | |||
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| Services immediately. | |
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| The Outlet air temperature has exceeded | |
|
|
|
|
|
|
|
| its maximum set point. The UPS will | |
|
|
|
|
|
|
|
| transfer the load to bypass if available. If | |
|
|
|
|
|
|
|
| already on bypass the system will | |
|
|
|
|
|
|
|
| shutdown. The fault will clear when the | |
|
|
|
|
|
|
|
| temperature falls below the Outlet Air | |
|
|
|
|
|
|
|
| Overtemp Warning threshold. (If this fault | |
Ups Ambient |
| UPS Ambient | Fault | YES | YES | YES | YES | doesn’t clear soon enough it will lead to an | |
Limit |
| Ot Limit | “overtemp | ||||||
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
| is still running when the fault clears it will | |
|
|
|
|
|
|
|
| auto retransfer to UPS. Check all air inlets | |
|
|
|
|
|
|
|
| and exhausts for blockage and check the | |
|
|
|
|
|
|
|
| air filter. Check the actual load against the | |
|
|
|
|
|
|
|
| UPS rating. Remove any excess load. | |
|
|
|
|
|
|
|
| Contact Liebert Global Services if the alarm | |
|
|
|
|
|
|
|
| persists. | |
|
|
|
|
|
|
|
| Failure of this fuse will remove control | |
|
|
|
|
|
|
|
| power. The UPS will attempt to transfer to | |
Pwr Supply |
| Power Supply | Fault | NO | YES | NO | YES | Static Bypass if available. Locate the cause | |
F1 Fail |
| F1 Fail | of any failure, before replacing a fuse or | ||||||
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
| Contact Liebert Global Services | |
|
|
|
|
|
|
|
| Immediately. | |
|
|
|
|
|
|
|
| UPS will transfer to Static Bypass if | |
SWGR Power | SWGR Power | Fault | NO | YES | NO | YES | available and shut down the UPS. | ||
Fail |
| Fail | will be inhibited. Contact Liebert Global | ||||||
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
| Services. | |
|
|
|
|
|
|
|
|
|
78