Operation

External Maintenance Bypass Switch Configurations

The External Maintenance Bypass Switch has three configuration options:

External maintenance bypass installed with interlock option

External maintenance bypass installed without interlock option

Not installed

Table 4

External maintenance switch configuration options

 

 

 

External

 

 

Maintenance Switch

Option Auxiliary Contact

 

Options

Status

User Prompt

 

 

open = On Test position or

Prompts the user to rotate to On Line position,

 

 

Maintenance position, or jumper

Installed with

Just before retransfer.

removed

Interlock Option

 

 

closed = On “ON LINE” position

Manual or automatic start (one button) is

 

 

 

 

(default jumper)

allowed all the way to load being On-line

 

 

 

 

 

 

open = jumper removed

Prompts the user to install jumper just before

 

 

retransfer”

Not installed

 

closed = default jumper

Manual or automatic start (one button) is

 

 

 

 

allowed all the way to load being On-line

 

 

 

 

 

 

 

 

 

Open = Jumper removed

Prompts the user to install jumper just before

Installed without

retransfer”

 

interlock option

 

 

Closed = default jumper

Prompts the user to verify the switch is in on-

 

 

line position before a retransfer is allowed

 

 

 

Regardless of how the configuration is set, if the auxiliary contacts are open, the user is unable to issue a retransfer command through the manual transfer / retransfer screen.

If the option is installed and the auxiliary contact status is read as switch is in the Bypass or Mainte- nance position, the “critical load shutdown” message reads “UPS off”.

Multiple Battery Cabinets

The Npower system offers an option allowing for the installation of more than two battery cabinets. The option consists of a Multiple Battery Breaker (MBB) board that mounts on the control door and an Input Contact Isolator (ICI) board that mounts in the option area (See the Multiple Battery Breaker Option in the options manual.)

The ICI board allows the Npower system to sense multiple battery cabinets, and the MBB board allows the UPS to support multiple battery cabinets by supplying power to the UVR coil of additional battery cabinets.

To access the screen for setting the number of battery cabinets in the system, navigate from the MAIN MENU to CONFIGURATION to SYSTEM SETTINGS, page 3. Select NUMBER OF BAT- TERY CABINETS to bring up the following password-protected screen.

Figure 29 Set number of battery cabinets screen

NUMBER OF BATTERY CABINETS

MIN 1

MAX 6

Set the number of battery cabinets by changing the number in the highlighted box. Pressing SELECT will save this information and return Operator to the System Settings Screen.

32

Page 40
Image 40
Liebert 30-130kVA manual Multiple Battery Cabinets, External Maintenance Bypass Switch Configurations