Operation

In this example, power is available from the normal and bypass sources, as well as from the battery. Notice that the switching devices are all closed except for the bypass switch at the top. The load is operating on conditioned power from the inverter. The battery is being charged by the rectifier. The static switch is operative and ready to respond to momentary demands for overload current.

Figure 11 Mimic display screen example: utility fail

SS

RECT.

BATTERY

DISCHG

INV. LOAD

FAULTS

In this example, we see that a utility failure has shut down both the normal and bypass power sources. The battery is connected and supplying power to the load.

MAIN MENU

 

 

MANUAL TRANSFER

 

 

 

 

BATTERY MANAGEMENT

STARTUP / SHUTDOWN

STATUS REPORTS

 

CONFIGURATION

 

Figure 12 Mimic display screen example: load on bypass, UPS module on and charging battery

MIMIC DISPLAY

BP

SS

 

 

RECT.

INV.

LOAD

BATTERY

 

 

 

 

 

 

 

FAULTS / ALARMS

 

 

 

 

 

 

 

CHARGE

 

 

 

 

 

 

 

 

 

22

Page 30