Theory of Operation
Nonlinear Load Characteristics
Computers and computer equipment with switching power supplies generate nonlinear currents rich in fifth and seventh harmonics.
The inverter
Unbalanced Load Characteristics
Unbalanced loads are actively regulated. The
2.2.5Static Bypass Switch
A static bypass switch is an integral part of the UPS. An automatic transfer control circuit senses the status of the operator controls, UPS logic signals and alarm messages, and critical bus operating con- ditions. If the inverter output can no longer supply the critical load, the static bypass switch automat- ically transfers the critical load to the bypass source without interruption.
Static Switch Backfeed Protection
The static bypass system is equipped with redundant disconnect circuits that prevent backfeed of lethal voltage to the bypass input in the event of a shorted static switch SCR. If a shorted SCR is detected, the static bypass switch is isolated and an alarm is annunciated at the UPS control panel, while the critical load remains on UPS output power.
Pulsed Parallel Operation
When an overload condition such as magnetic inrush current or a branch load circuit fault exceeds 200% of the
Load Transfers
Transfers to (transfer) or from (retransfer) the bypass may be performed automatically or manually in a
Manual load transfers and retransfers are initiated by the Operator from the UPS Control Panel.
Automatic transfers are initiated by the UPS system control logic when an overload is beyond the specified capabilities of the UPS inverter or when a fault occurs within the UPS module. An auto- matic retransfer is initiated if this function is enabled and if system conditions for a retransfer are present.
12