Operation

Options

This multiple-page screen, accessed from the third page of the SYSTEM SETTINGS screen, enables and disables optional features which might or might not be installed in your UPS. To enable or dis- able one of these options, do the following:

1.Highlight the option you wish to enable or disable.

2.Press UP or DOWN to toggle between enabled or disabled.

3.Press SELECT to set the desired status.

NOTE

Some of the options appearing on the following screens are reserved for future development.

Figure 50 Options screen, page 1

OPTIONS

ACTIVE FILTER

NO

LBS

NO

GENERATOR

NO

AUTO RESTART

NO

 

 

 

 

 

N

EXT

 

EXIT

 

NEXT

 

 

 

 

 

Highlighting 10% PASSIVE OPTIONS and pressing SELECT will bring up the following screen allowing the Operator to decide whether or not the input trap filter should be disconnected at light loads to prevent a leading power factor at the input. For more information, see Input Trap Filter in the options manual.

Figure 51 10% passive filter settings screen

10% PASSIVE FILTER SETTINGS

FILTER DISCONNECT LEVEL

0

FILTER PREFERRED STATE

CLOSED

10% PASSIVE FILTER CONTACTOR

DISABLE

EXIT

 

43

Page 51
Image 51
Liebert 30-130kVA manual Options, 10% Passive Filter Settings, Active Filter LBS Generator Auto Restart