Operation

Table 7

Alarms, functions, and corrective actions (continued)

 

 

 

 

 

 

 

 

 

 

Actual

 

 

 

 

 

 

 

 

Alarm/fault

 

 

 

 

 

 

 

 

Name

 

 

 

 

 

 

 

 

Displayed

 

Description

Fault

 

 

 

 

 

On Front

 

of Alarm/

Or

Latch

Dial

Freeze

Event Log

 

Panel

 

Fault

Alarm

Mask

Mask

Mask

Mask

Meaning and Corrective Action(s)

 

 

 

 

 

 

 

 

With the Batt Gnd Fault option installed and

Batt Gnd

 

Battery ground

Alarm

NO

YES

NO

YES

the batt breaker closed, the DSP sees its

Fault

 

fault alarm

BGF input asserted by the SWGR. No

 

 

 

 

 

 

 

 

 

 

 

 

 

 

action required.

 

 

 

 

 

 

 

 

 

Aux Ovtemp

 

Aux Overtemp

 

 

 

 

 

With the Auxiliary temp sensor installed, it

 

Alarm

YES

YES

NO

YES

is reading 85% or more of the specified

Warning

 

Warning

 

 

 

 

 

 

Maximum Aux temperature set point value.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Batt Ovtemp

 

Battery

 

 

 

 

 

With the battery breaker closed the battery

 

Overtemp

Alarm

NO

YES

NO

YES

has exceeded the “Battery Temperature

Warning

 

 

Warning

 

 

 

 

 

Alarm Threshold” set point value.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Sensors on the power semiconductor

 

 

 

 

 

 

 

 

heatsinks detect temperatures above the

 

 

 

 

 

 

 

 

steady state limits for these components.

 

 

Heatsink

 

 

 

 

 

The control logic sets off the alarm but does

Heatsink

 

 

 

 

 

 

not shut down the UPS module if the

 

Overtemp

Alarm

NO

YES

NO

YES

Ovtemp

 

condition lasts less than 10 minutes. Check

 

Warning

 

 

 

 

 

 

 

 

 

 

 

 

the air intake, air exhaust, and filters.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Reduce the load or transfer it to bypass.

 

 

 

 

 

 

 

 

Contact Liebert Global Services if the alarm

 

 

 

 

 

 

 

 

persists.

 

 

 

 

 

 

 

 

The intake air to the UPS module exceeds

 

 

Inlet Air

 

 

 

 

 

the specified maximum temperature. This

Inlet Air

 

 

 

 

 

 

condition only causes an alarm, but should

 

Overtemp

Alarm

NO

YES

NO

YES

be corrected immediately to prevent

Ovtemp

 

 

Warning

 

 

 

 

 

equipment overheating. Check to make

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

sure nothing is blocking the inlet air and that

 

 

 

 

 

 

 

 

the air filter is clean.

Ups Ambient

 

UPS Ambient

 

 

 

 

 

The Outlet air temperature has exceeded

 

Alarm

NO

YES

NO

YES

85% of its “Maximum outlet air temperature”

OvTemp

 

OvTemp

 

 

 

 

 

 

limit.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A fault in the designated Fan motor has

 

 

 

 

 

 

 

 

occurred. This condition only causes an

 

 

 

 

 

 

 

 

alarm, but if not promptly corrected it could

Pwr pole Fan

Power pole

Alarm

NO

YES

NO

YES

cause an equipment over-temperature

1 Fail

 

Fan 1 Fail

condition that would shut down the UPS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Module. Check the Fans for proper

 

 

 

 

 

 

 

 

operation. Contact Liebert Global Services

 

 

 

 

 

 

 

 

if you require assistance or to replace a fan.

 

 

 

 

 

 

 

 

A fault in the designated Fan motor has

 

 

 

 

 

 

 

 

occurred. This condition only causes an

 

 

 

 

 

 

 

 

alarm, but if not promptly corrected it could

Pwr pole Fan

Power pole

Alarm

NO

YES

NO

YES

cause an equipment over-temperature

2 Fail

 

Fan 2 Fail

condition that would shut down the UPS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Module. Check the Fans for proper

 

 

 

 

 

 

 

 

operation. Contact Liebert Global Services

 

 

 

 

 

 

 

 

to replace a fan.

 

 

 

 

 

 

 

 

A fault in the designated Fan motor has

 

 

 

 

 

 

 

 

occurred. This condition only causes an

 

 

 

 

 

 

 

 

alarm, but if not promptly corrected it could

Pwr pole Fan

Power pole

Alarm

NO

YES

NO

YES

cause an equipment over-temperature

3 Fail

 

Fan 3 Fail

condition that would shut down the UPS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Module. Check the Fans for proper

 

 

 

 

 

 

 

 

operation. Contact Liebert Global Services

 

 

 

 

 

 

 

 

to replace a fan.

84

Page 92
Image 92
Liebert 30-130kVA manual Condition only causes an alarm, but should