Operation
Table 7 | Alarms, functions, and corrective actions (continued) |
| |||||||
|
|
|
|
|
|
|
|
| |
Actual |
|
|
|
|
|
|
|
| |
Alarm/fault |
|
|
|
|
|
|
|
| |
Name |
|
|
|
|
|
|
|
| |
Displayed |
| Description | Fault |
|
|
|
|
| |
On Front |
| of Alarm/ | Or | Latch | Dial | Freeze | Event Log |
| |
Panel |
| Fault | Alarm | Mask | Mask | Mask | Mask | Meaning and Corrective Action(s) | |
|
|
|
|
|
|
|
| With the load on Static Bypass, the phase A | |
|
|
|
|
|
|
|
| output kVA or kW or RMS current has | |
|
|
|
|
|
|
|
| exceeded 115% of the nominal | |
SBS Ovld |
| SBS Overload | Alarm | NO | NO | NO | YES | kVA or kW or RMS current rating. The UPS | |
Phase A |
| Phase A | will show time remaining until a shutdown | ||||||
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
| will occur, per the Overload vs. time curve. | |
|
|
|
|
|
|
|
| The alarm will clear when the overload falls | |
|
|
|
|
|
|
|
| to below 110% of the rating. | |
|
|
|
|
|
|
|
| With the load on Static Bypass, the phase B | |
|
|
|
|
|
|
|
| output kVA or kW or RMS current has | |
|
|
|
|
|
|
|
| exceeded 115% of the nominal | |
SBS Ovld |
| SBS Overload | Alarm | NO | NO | NO | YES | kVA or kW or RMS current rating. The UPS | |
Phase B |
| Phase B | will show time remaining until a shutdown | ||||||
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
| will occur, per the Overload vs. time curve. | |
|
|
|
|
|
|
|
| The alarm will clear when the overload falls | |
|
|
|
|
|
|
|
| to below 110% of the rating. | |
|
|
|
|
|
|
|
| With the load on Static Bypass, the phase C | |
|
|
|
|
|
|
|
| output kVA or kW or RMS current has | |
|
|
|
|
|
|
|
| exceeded 115% of the nominal | |
SBS Ovld |
| SBS Overload | Alarm | NO | NO | NO | YES | kVA or kW or RMS current rating. The UPS | |
Phase C |
| Phase C | will show time remaining until a shutdown | ||||||
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
| will occur, per the Overload vs. time curve. | |
|
|
|
|
|
|
|
| The alarm will clear when the overload falls | |
|
|
|
|
|
|
|
| to below 110% of the rating. | |
|
|
|
|
|
|
|
| The instantaneous inverter current of any | |
Inverter I |
| Inverter |
|
|
|
|
| one phase has exceeded its | |
| Alarm | NO | NO | NO | YES | current limit value. The UPS will shutdown | |||
Limit |
| Current Limit | |||||||
|
|
|
|
|
| when the Current Overload vs. time curve is | |||
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| exceeded. | |
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| Output frequency differs from the nominal | |
Output OF/UF | Output OF/UF | Alarm | NO | YES | NO | YES | (60Hz) by more than 0.5Hz. No transfer or | ||
shutdown occurs. Contact Liebert Global | |||||||||
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| Services at once. | |
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| With the load on UPS, Phase x output KVA | |
|
|
|
|
|
|
|
| or KW or RMS current has exceeded 105% | |
|
| Inverter |
|
|
|
|
| of the nominal per phase rating. The UPS | |
Inv Ovld |
|
|
|
|
|
| will begin sending the time remaining until a | ||
| Overload | Alarm | NO | YES | NO | YES | |||
Phase A |
| transfer or shutdown will occur, per the | |||||||
| Phase A |
|
|
|
|
| |||
|
|
|
|
|
|
| Overload vs. Time Curve. The alarm | ||
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| condition will clear when the overload | |
|
|
|
|
|
|
|
| returns to below the nominal rating. | |
|
|
|
|
|
|
|
| With the load on UPS, Phase A output kVA | |
|
|
|
|
|
|
|
| or kW or RMS current has exceeded 105% | |
|
| Inverter |
|
|
|
|
| of the nominal per phase rating. The UPS | |
Inv Ovld |
|
|
|
|
|
| will begin sending the time remaining until a | ||
| Overload | Alarm | NO | YES | NO | YES | |||
Phase B |
| transfer or shutdown will occur, per the | |||||||
| Phase B |
|
|
|
|
| |||
|
|
|
|
|
|
| Overload vs. Time Curve. The alarm | ||
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| condition will clear when the overload | |
|
|
|
|
|
|
|
| returns to below the nominal rating. |