Operation

The DC BUS/BATTERY status screen displays the following real-time data:

DC Bus Volts

Battery Volts

Battery Current (Chg/disch)

Battery Temperature (This reading is the temperature of the ambient air in the battery cabinet.)

Battery Time Remaining

3.BYPASS INPUT. Selecting BYPASS from the Monitor Mimic Display displays the following screen showing bypass input voltage and the bypass input frequency. Press SELECT to return to the Monitor Mimic Display.

Figure 17 Bypass input status

BYPASS INPUT STATUS

A

V L - L 213

BC FREQ. 59.9 HZ

213 214 PHASE DIFF 0

The Bypass Input Block displays the following real-time data:

Bypass AC Volts AB, BC, CA

Bypass Frequency

Bypass Phase Difference

4.OUTPUT / LOAD. Select LOAD from the Monitor Mimic Display screen to bring up this block. It displays total output power to the critical load in kVA and kW. The critical load current per phase is also displayed in this block. Note that kW is not displayed when the load is on the bypass line. During an overload condition, the time remaining before transfer is displayed at the bottom of the load box. Press SELECT to return to the Mimic Display Screen.

Figure 18 Output load status screen

OUTPUT LOAD STATUS

 

A

B

C

FREQ.

59.9 HZ

V L-L 205

203

207

V L-N 120

117

118

% OF RATED LOAD:

I

5

5

162

KVA

42 %

KVA

1

1

19

KW

42 %

KW

1

1

15

OVLD COND (SEC.)

25

Page 33
Image 33
Liebert 30-130kVA manual Bypass Input Status, Output Load Status, Freq .9 HZ 213 214 Phase Diff