Operation
Table 7 | Alarms, functions, and corrective actions (continued) |
| ||||||
|
|
|
|
|
|
|
|
|
Actual |
|
|
|
|
|
|
|
|
Alarm/fault |
|
|
|
|
|
|
|
|
Name |
|
|
|
|
|
|
|
|
Displayed |
| Description | Fault |
|
|
|
|
|
On Front |
| of Alarm/ | Or | Latch | Dial | Freeze | Event Log |
|
Panel |
| Fault | Alarm | Mask | Mask | Mask | Mask | Meaning and Corrective Action(s) |
|
|
|
|
|
|
|
| With the load on UPS, PhaseB output KVA |
|
|
|
|
|
|
|
| or KW or RMS current has exceeded 105% |
|
| Inverter |
|
|
|
|
| of the nominal per phase rating. The UPS |
Inv Ovld |
|
|
|
|
|
| will begin sending the time remaining until a | |
| Overload | Alarm | NO | YES | NO | YES | ||
Phase C |
| transfer or shutdown will occur, per the | ||||||
| Phase C |
|
|
|
|
| ||
|
|
|
|
|
|
| Overload vs. Time Curve. The alarm | |
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| condition will clear when the overload |
|
|
|
|
|
|
|
| returns to below the nominal rating. |
|
| Low Power |
|
|
|
|
| On any output phase that is supplying at |
Low Pwr |
|
|
|
|
|
| least 15% of its rated KVA, the measured | |
| Factor | Alarm | NO | YES | NO | YES | ||
Factor Warn |
| output power factor is below 0.50, leading | ||||||
| Warning |
|
|
|
|
| ||
|
|
|
|
|
|
| or lagging. | |
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| With the load being supplied by the inverter, |
|
|
|
|
|
|
|
| the measured load current exceeds the |
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| Pulse Current Limit set point values. If the |
Pulse |
| Pulse Parallel |
|
|
|
|
| Static Bypass is available, the SBS supplies |
| Alarm | NO | YES | NO | YES | supplemental power. If at the end of 10 | ||
Paralleling |
| Activated | ||||||
|
|
|
|
|
| cycles the load current has not returned to | ||
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| below 105%, the Static Bypass will be left |
|
|
|
|
|
|
|
| on and the inverter will be turned off. If the |
|
|
|
|
|
|
|
| over current has cleared the Inverter will be |
|
|
|
|
|
|
|
| left on and the SBS will be turned off. |
|
|
|
|
|
|
|
| After performing a recoverable transfer to |
|
|
|
|
|
|
|
| bypass, with Auto Rexfer enabled, the Auto |
|
|
|
|
|
|
|
| Rexfer time out (default=5minutes) has |
|
| Auto |
|
|
|
|
| elapsed before retransfer could be |
Auto rexfer |
|
|
|
|
|
| performed. A manual retransfer must be | |
| Retransfer | Alarm | YES | YES | NO | YES | ||
failed |
| performed, which will then clear the lockout | ||||||
| Failed |
|
|
|
|
| ||
|
|
|
|
|
|
| and zero the retransfer/ hour counter. If the | |
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| manual transfer is inhibited, the Inverter |
|
|
|
|
|
|
|
| may be latched off due to another fault. |
|
|
|
|
|
|
|
| Contact Liebert Global Services. |
|
|
|
|
|
|
|
| The UPS has determined that the actual |
|
|
|
|
|
|
|
| number of Auto Retransfers in the past hour |
|
|
|
|
|
|
|
| has exceeded the permitted maximum. |
Excessive |
| Excessive |
|
|
|
|
| (user settable, default=5). This alarm |
| Auto | Alarm | YES | YES | NO | YES | should not be issued if auto retransfers are | |
Auto Rexfer |
| |||||||
| Retransfer |
|
|
|
|
| disabled by setting the maximum attempts | |
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| to “0”. A manual retransfer must be |
|
|
|
|
|
|
|
| performed, which will then clear the lockout |
|
|
|
|
|
|
|
| and zero the retransfer/hour counter. |
|
|
|
|
|
|
|
| If the unit is supplying power to an Auxiliary |
Aux Power |
| Aux Power Fail | Alarm | NO | YES | NO | YES | device, this alarm indicates that the system |
Fail |
| has detected a failure in the Aux. Power | ||||||
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| circuit. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| If the unit is supplying power to an Auxiliary |
EPO Power |
| EPO Power | Alarm | NO | YES | NO | YES | device, this alarm indicates that the system |
Fail |
| Fail | has detected a failure in the Aux. Power | |||||
|
|
|
|
|
| |||
|
|
|
|
|
|
|
| circuit. |
|
|
|
|
|
|
|
|
|
LBS Power |
| LBS Power |
|
|
|
|
| Power to the Load Bus Sync circuit has |
| Alarm | NO | YES | NO | YES | been lost. Check external wiring. Contact | ||
Fail |
| Fail | ||||||
|
|
|
|
|
| Liebert Global Services. | ||
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|