Operation

Table 7

Alarms, functions, and corrective actions (continued)

 

 

 

 

 

 

 

 

 

 

Actual

 

 

 

 

 

 

 

 

Alarm/fault

 

 

 

 

 

 

 

 

Name

 

 

 

 

 

 

 

 

Displayed

 

Description

Fault

 

 

 

 

 

On Front

 

of Alarm/

Or

Latch

Dial

Freeze

Event Log

 

Panel

 

Fault

Alarm

Mask

Mask

Mask

Mask

Meaning and Corrective Action(s)

 

 

 

 

 

 

 

 

The generator option is installed, the

Delayed Batt

 

Delayed

 

 

 

 

 

system is on generator and the “Delayed

 

Alarm

NO

NO

NO

YES

Battery Charge” is suppressing battery

Charge

 

Battery Charge

 

 

 

 

 

 

 

 

charging to reduce the load on the

 

 

 

 

 

 

 

 

generator.

Reduced I

 

Reduced

 

 

 

 

 

The UPS recognizes that the source is a

 

Alarm

NO

NO

NO

YES

generator and has reduced the current limit

Limit

 

Current Limit

 

 

 

 

 

 

setting to avoid generator overloading.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Per the user request, all event logs have

Event Log

 

Event Log

Alarm

NO

NO

NO

YES

been cleared. This will be the first alarm in

Clear

 

Clear

the new log. Momentary display. Sets flag

 

 

 

 

 

 

 

 

 

 

 

 

 

 

in the event history log.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

With the battery breaker closed, the battery

 

 

 

 

 

 

 

 

voltage has not reached 95% of the units

Batt Not

 

Battery Not

 

 

 

 

 

“DC Float Voltage” set point within a

 

Alarm

YES

NO

NO

YES

calculated time (based on the test duration.)

Charging

 

Charging

 

 

 

 

 

 

This calculation will start immediately at the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

end of a successful (“Passed”) battery self

 

 

 

 

 

 

 

 

test.

 

 

 

 

 

 

 

 

The UPS has detected a communication

UPSC-MM

 

UPSC-MM

Alarm

YES

YES

NO

YES

failure between its UPS controls and it

comm. Fail

 

Comm Fail

monitoring system. Contact Liebert Global

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Service.

 

 

 

 

 

 

 

 

 

User

 

User

 

 

 

 

 

The User has initiated an “Inverter Off” or

 

Alarm

YES

YES

NO

YES

“System Shutdown” through the User

Shutdown

 

Shutdown

 

 

 

 

 

 

Shutdown screen.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cant Exec

 

Cannot

 

 

 

 

 

The battery test could not be performed.

 

Execute

Alarm

NO

NO

NO

YES

See 3.3.7 - Battery Management.

Batt Test

 

 

Battery Test

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Batt Not

 

Battery Not

Alarm

NO

NO

NO

YES

A battery test cannot be executed because

Charged

 

Charged

the battery charge is less than 90%.

 

 

 

 

 

 

Sys Time Set

System Time

 

 

 

 

 

The User has changed the Date or Time

Set By

Alarm

YES

YES

NO

YES

from the front Panel. Momentary display.

By Op

 

 

Operator

 

 

 

 

 

Sets flag in the event history log.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The User has ordered a manual transfer

Manual XFER

Manual

Alarm

NO

NO

NO

YES

from UPS to Bypass from the front panel

Transfer

controls. Momentary display. Sets flag in

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

the event history log.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The User has ordered a manual transfer

Manual

 

Manual

Alarm

NO

NO

NO

YES

from Bypass to UPS from the front panel

ReXFER

 

Retransfer

controls. Momentary display. Sets flag in

 

 

 

 

 

 

 

 

 

 

 

 

 

 

the event history log.

 

 

 

 

 

 

 

 

 

Batt Cycle

 

 

 

 

 

 

 

With batt breaker closed, Monitor has

 

Battery Cycle

Alarm

NO

NO

NO

YES

determined that the buffer that keeps track

Buff Full

 

Buffer Full

of the number of hits the battery has taken

 

 

 

 

 

 

 

 

 

 

 

 

 

 

is full. No action required.

 

 

 

 

 

 

 

 

 

86

Page 94
Image 94
Liebert 30-130kVA manual See 3.3.7 Battery Management