Schneider Electric 66846, 66074 user manual STS Notified Applications

Page 48

Network

Management Card

User Manual

This page is used to define either the shutdown or the notification settings used by the Network Shutdown Modules that connect to Network Management Card. These settings are used by the Network Shutdown Modules if they are in centralized-configuration mode or if their configuration is not valid.

Shutdown After (time before shutdown) This is the time in seconds that the system waits following failure of AC power before initiating the system-shutdown procedure. This value must be selected to provide users with enough time to close their applications and disconnect, but within the battery backup time provided by the UPS.

If another criterion occurs before the end of the shutdown timer, the shutdown procedure is immediately run.

This parameter is optional, uncheck it to invalidate

Shutdown Duration : This is the time in seconds required by the system to go through its shutdown procedure.

Broadcast : Send network notifications to the Administrators and Users groups on events

If you wish to set up a new configuration for the Network Shutdown Modules already set to centralized- configuration mode, proceed as indicated below.

Change the Network Shutdown Module parameters in the page “Central Shutdown Configuration”.

Click the Save button. Open the List of notified applications.

Select the Network Shutdown Modules to receive the new configuration.

Press the button “Remove” They reconnect and use the new configuration

3.5.5 STS Notified Applications

Click the “Notified Application” section in the menu.

Security: the administrator has to enter his login/password to view this information.

This menu enables:

The addition of the supervision stations receiving traps and configuration of the trap type.

To list all the Notified Applications and the main parameters.

Simulate events to test notification and shutdown of the Notified Applications.

Up to 50 destinations can be managed by the card.

Network Management Card – User Manual

34003676EN/HA

Page 48/81

Image 48
Contents Network Management Card NMC Transverse Environment Sensor Network Management Card Configuration Configuration VIA Telnet Configuration VIA SSHMAINTENANCE72 Software Upgrade Appendices Tables of Alarms and EventsGlossary Connecting the UPS / STS to the Network IntroductionNetwork Management Card MGE supervisor Enterprise Power Manager Protecting the computers / serversMonitoring the UPSs over the network Network Shutdown module only available for UPS, not for STSHow to connect UPS / network Setting up the protection, for UPS onlyConnection Presentation of the Network Management Cards NMCPresentation of the Environment Sensor solution Direct sending of E-mailSending text messages SMS Technical data 10/81 Installation Basic configurationEnvironment Sensor Supervision / Administration via a Web browser Optimising the performance of your browserUPS / STS UPS propertiesUPS zone general information on the UPS UPS status zone essential informationBattery status zone STS properties STS zone general information on the STSSTS status zone essential information About Sources status zoneOn-line help 18/81 UPS 3-Phase display Normal input measurementsBattery measurements By Pass measurementsSTS 3-Phase display UPS Control Source 2 input measurement23/81 UPS weekly schedule programming Shutdown parameters Important noteViewing the alarms Logs UPS MeasurementsSTS Measurements 29/81 UPS Event log STS Event log31/81 System log 33/81 Notification UPS Email NotificationNotified events Mail message configuration see next Recipient ListOther settings STS Email NotificationEmail Message Settings UPS Email Message SettingsSender SubjectSTS Email Message Settings Email Example Configuration User Name and password by default are MgeupsNetwork Settings 42/81 System 44/81 UPS Notified Applications 46/81 Central Shutdown Configuration STS Notified Applications 49/81 Access control 51/81 Access is disabled and the card is accessible in SSH Time Characteristics Status Configuration LogEnvironment Environment status 56/81 UPS Environment Settings UPS Environment SettingsSTS Environment Settings Humidity4 Log Set-up of the shutdown parameters Shutdown criteria managed by the Management CardSpecific set-up for long autonomy installation 30 mn Shutdown when backup time is less thanShutdown duration Different server and UPS shutdown sequences 63/81 4 Off/On command Configuring a set of cards with Mupgrade Configuration in local modeChoice 1 Snmp agent configuration menu MgeupsChoice 3 Access control Choice 2 UPS / STS parametersChoice 4 Restore default configuration Choice 5 Reset the cardConfiguration via Telnet Configuration via SSHPuTTY SSH Client Program 70/81 71/81 Software upgrade Card firmware upgrade using Mupgrade WindowsCard software upgrade via Tftp Unix and Windows Tables of alarms and events UPS Alarm tableSTS Alarm table English FrenchUPS event table UPS STS event table 77/81 System alarm table Glossary Subnet mask TelnetTrap Snmp