User Manual

3.2.9 Shutdown parameters

Click on the “Shutdown parameters” section in the menu to see the list of parameters.

Important note:

For installations that do not use Network Shutdown Module (backup units, routers and other internetworking equipment, automated systems, etc.) or in the event of long backup periods, the card will send a command to the UPS (dependant of the UPS settings and UPS type) to shut off end of the programmed Shutdown After time. To prevent this, the Shutdown After box must be not selected (default)

This page enables viewing and configuration of UPS operation parameters in battery mode and for power restoration.

When you tick the Show advanced parameters option, extra parameters are displayed. These parameters enable, in particular, adjustment of certain thresholds related to the percentage of remaining battery charge level.

The Output column enables each output to be named (maximum 30 characters).

Note

For the output

Shutdown after is the operating time in minutes left for users after a switch to backup before starting the shutdown sequences of the UPS and its equipment (from 0 to 1092).

If remaining time under (from 0 to 9999 seconds) and If Capacity under (from 0 to 100%) are two extra conditions for remaining backup time and battery level that can trigger shutdown sequences before the “Shutdown after” period runs out

Shutdown duration is the time required for complete shutdown of systems when a switch to backup time is long enough to trigger the shutdown sequences. It is calculated automatically at the maximum of Shutdown duration of subscribed clients but can be modified in the Advanced mode

Restart after is the minimum shutdown time before restarting the UPS after a shutdown sequence. It is thus possible to limit repeated restarts that may be due to several successive utility failures.

If the Battery is charged for and If Capacity exceeds are two extra conditions for minimum battery level and maximum recharge time to be reached before restarting the UPS after utility restoration

Security: The administrator has to click on Save and enter his login/password to save any modifications. The

default login and password are: MGEUPS

Network Management Card – User Manual

34003676EN/HA

Page 25/81

Image 25
Contents Network Management Card NMC Transverse Environment Sensor Network Management Card Configuration VIA Telnet Configuration VIA SSH ConfigurationMAINTENANCE72 Software Upgrade Appendices Tables of Alarms and EventsGlossary Introduction Connecting the UPS / STS to the NetworkNetwork Management Card Protecting the computers / servers MGE supervisor Enterprise Power ManagerMonitoring the UPSs over the network Network Shutdown module only available for UPS, not for STSSetting up the protection, for UPS only How to connect UPS / networkConnection Presentation of the Network Management Cards NMCDirect sending of E-mail Presentation of the Environment Sensor solutionSending text messages SMS Technical data 10/81 Basic configuration InstallationEnvironment Sensor Optimising the performance of your browser Supervision / Administration via a Web browserUPS properties UPS / STSUPS zone general information on the UPS UPS status zone essential informationBattery status zone STS zone general information on the STS STS propertiesSTS status zone essential information Sources status zone AboutOn-line help 18/81 Normal input measurements UPS 3-Phase displayBy Pass measurements Battery measurementsSTS 3-Phase display Source 2 input measurement UPS Control23/81 UPS weekly schedule programming Important note Shutdown parametersViewing the alarms UPS Measurements LogsSTS Measurements 29/81 STS Event log UPS Event log31/81 System log 33/81 UPS Email Notification NotificationNotified events Recipient List Mail message configuration see nextSTS Email Notification Other settingsUPS Email Message Settings Email Message SettingsSender SubjectSTS Email Message Settings Email Example User Name and password by default are Mgeups ConfigurationNetwork Settings 42/81 System 44/81 UPS Notified Applications 46/81 Central Shutdown Configuration STS Notified Applications 49/81 Access control 51/81 Access is disabled and the card is accessible in SSH Time Status Configuration Log CharacteristicsEnvironment Environment status 56/81 UPS Environment Settings UPS Environment SettingsHumidity STS Environment Settings4 Log Shutdown criteria managed by the Management Card Set-up of the shutdown parametersShutdown when backup time is less than Specific set-up for long autonomy installation 30 mnShutdown duration Different server and UPS shutdown sequences 63/81 4 Off/On command Configuration in local mode Configuring a set of cards with MupgradeMgeups Choice 1 Snmp agent configuration menuChoice 2 UPS / STS parameters Choice 3 Access controlChoice 5 Reset the card Choice 4 Restore default configurationConfiguration via SSH Configuration via TelnetPuTTY SSH Client Program 70/81 71/81 Card firmware upgrade using Mupgrade Windows Software upgradeCard software upgrade via Tftp Unix and Windows UPS Alarm table Tables of alarms and eventsSTS Alarm table English FrenchUPS event table UPS STS event table 77/81 System alarm table Glossary Telnet Subnet maskTrap Snmp