Network
Management Card
User Manual
3.6.3 UPS Environment Settings
3.6.3.1 UPS Environment Settings
The environment sensor measures temperature, humidity and gives the status of the 2 contacts (used for door, alarms or generator unit).
The temperature and humidity thresholds can be adjusted and can trigger notification and correct shutdown of the protected system.
The Sensor name is the function name given to the sensor, usually it enables location of the sensor. Temperature: choose the temperature unit (°C or °F) from the se lection box.
High threshold: if this value is exceeded, a notification is sent if this is validated. Default value is 40 °C / 104 °F.
Low threshold: if this value is exceeded, a notification is sent if this is validated. Default value is 5 ° C / 41 °F.
Hysteresis must be set to prevent multiple notifications if temperature fluctuates around a threshold. Default value is 2 °C / 3.6 °F. (Advanced parameter s)