Schneider Electric 66846, 66074 user manual 46/81

Page 46

Network

Management Card

User Manual

Shutdown after : is the time available to the user from the Power failure until the launch of the shutoff sequence of the UPS. This parameter is optionnal.

Many actions are available on this page :

Remove : Depending on the kind of application, the selected ones will definitively disappear from the table as SNMP applications, or they will disappear and automatically re-subscribe as the Network Shutdown Module application.

Utility failure Test : Two alarms 'Utility failure' and 'Utility restored' spaced of 60 seconds will be sent to the applications selected, making sure that the applications can be reached over the network.

Shutdown Test : This test simulates a UPS on battery operation, it sends alarms to the selected applications. It enables an easy check to see if the server protection works correctly.- No intervention on the UPS is required.

-Simulated alarms will be processed by the applications selected only.

-Warning :This test will generate a REAL shutdown sequence of servers on which Network Shutdown Module is running.

Add NMS allows to add a SNMP trap receiver as a Network Management System.

Modify NMS allows to modify a SNMP trap receiver.

Both buttons makes appear a new window where it is possible to enter the Application name, the Hostname or IP Address, the Trap community and the severity.

Network Management Card – User Manual

34003676EN/HA

Page 46/81

Image 46
Contents Network Management Card NMC Transverse Environment Sensor Network Management Card MAINTENANCE72 Software Upgrade ConfigurationConfiguration VIA Telnet Configuration VIA SSH Appendices Tables of Alarms and EventsGlossary Introduction Connecting the UPS / STS to the NetworkNetwork Management Card Monitoring the UPSs over the network MGE supervisor Enterprise Power ManagerProtecting the computers / servers Network Shutdown module only available for UPS, not for STSConnection How to connect UPS / networkSetting up the protection, for UPS only Presentation of the Network Management Cards NMCDirect sending of E-mail Presentation of the Environment Sensor solutionSending text messages SMS Technical data 10/81 Basic configuration InstallationEnvironment Sensor Supervision / Administration via a Web browser Optimising the performance of your browserUPS zone general information on the UPS UPS / STSUPS properties UPS status zone essential informationBattery status zone STS zone general information on the STS STS propertiesSTS status zone essential information About Sources status zoneOn-line help 18/81 UPS 3-Phase display Normal input measurementsBattery measurements By Pass measurementsSTS 3-Phase display UPS Control Source 2 input measurement23/81 UPS weekly schedule programming Shutdown parameters Important noteViewing the alarms Logs UPS MeasurementsSTS Measurements 29/81 UPS Event log STS Event log31/81 System log 33/81 UPS Email Notification NotificationNotified events Mail message configuration see next Recipient ListOther settings STS Email NotificationSender Email Message SettingsUPS Email Message Settings SubjectSTS Email Message Settings Email Example Configuration User Name and password by default are MgeupsNetwork Settings 42/81 System 44/81 UPS Notified Applications 46/81 Central Shutdown Configuration STS Notified Applications 49/81 Access control 51/81 Access is disabled and the card is accessible in SSH Time Status Configuration Log CharacteristicsEnvironment Environment status 56/81 UPS Environment Settings UPS Environment SettingsSTS Environment Settings Humidity4 Log Set-up of the shutdown parameters Shutdown criteria managed by the Management CardShutdown when backup time is less than Specific set-up for long autonomy installation 30 mnShutdown duration Different server and UPS shutdown sequences 63/81 4 Off/On command Configuring a set of cards with Mupgrade Configuration in local modeChoice 1 Snmp agent configuration menu MgeupsChoice 3 Access control Choice 2 UPS / STS parametersChoice 4 Restore default configuration Choice 5 Reset the cardConfiguration via SSH Configuration via TelnetPuTTY SSH Client Program 70/81 71/81 Card firmware upgrade using Mupgrade Windows Software upgradeCard software upgrade via Tftp Unix and Windows STS Alarm table Tables of alarms and eventsUPS Alarm table English FrenchUPS event table UPS STS event table 77/81 System alarm table Glossary Subnet mask TelnetTrap Snmp