Powerware SOLA 4000 manual Input Cables / Fuses, Mm²

Page 22

SOLA 4000 - Installation and Initial Start-Up

1 Installation

Version 1 SOLA 4000 with Common Input for

Rectifier and Bypass

Input Cables / Fuses

Type

 

Input

Input

earth

SOLA

 

cables

fuses

cable

4000

 

[mm²]

[A]

[mm²]

 

 

 

 

 

10

 

4x10

25

16

15

 

4x10

35

16

20

 

4x16

50

16

30

 

4x25

63

25

40

 

4x35

100

25

60

 

4x35

125

25

80

 

4x70

160

50

100

 

4x70

200

50

120

 

4x120

250

70

 

 

 

 

 

TAB.1.2.1

UPS input cables

 

and fuses, version 1

Output / Battery Cables and Max. Cur- rent Ratings for Battery Overcurr. pro- tection

Type

Battery

Output cables

Max. inv. input

SOLA

cables

[mm²]

current

4000

[mm²]

(Vdc=320V)

 

 

 

 

 

10

2x16

4x10

25

15

2x16

4x10

40

20

2x25

4x16

50

30

2x25

4x35

75

40

2x35

4x25

100

60

2x50

4x35

150

80

2x70

4x50

200

100

2x95

4x70

250

120

2x120

4 x120

300

 

 

 

 

TAB.1.2.2 UPS output cables and fuses, version 1

JUE 401265

22

Image 22
Contents Uninterruptible Power Supply Sola 4000 Operating Manual Safety Instructions Safety InstructionsSola 4000 Operating Manual Safety Instructions UPS Assembly Sola 4000 General System Description ChaptersFeatures UPS AssemblySola 4000 General System Description Rectifier/Battery Charger UPS System StructureStatic Switches Battery AccumulatorInverter Under inverter failure conditions Maintenance Bypass Hot-Standby SystemsParallel-Redundant Systems Parallel SystemsFunctional Description Emergency Power OffOperating Panel Remote MonitoringAdditional START- UP Procedure for MULTI-UNIT SYSTEMS42 Sola 4000 Installation and Initial Start-Up ChaptersFiguresInstallation Initial START- UPSola 4000 Installation and Initial Start-Up Sola 4000 Installation and Initial Start-UpInstallation Mechanical InstallationWeight Floor Space RequiredRoom Size for 10-60 kVA UPS 6 UPS 10-60kVA room size JUERoom Size for 80-120 kVA UPS with auxiliary AC001 cabinet 7 UPS 80-120kVA room size JUERoom Size for 80-120 kVA UPS with auxiliary AC002 cabinet 8 UPS 80-120kVA room size JUEElectrical Installation General1 UPS connection diagram, version Input Cables / Fuses Mm²2 UPS connection diagram, version Input Cables Output / Battery CablesInput Fuses Installation of additional optional cabi- nets Sola 4000 with isolation transformer of the bypass supply3 UPS connection diagram, with THD filters Sola 4000 with THD filters4 Installation of 12-pulse units without galvanic isolation Sola 4000 with 12-pulse charger / rectifierInstallation of an External Maintenance Bypass 1 External Maintenance Bypass Switch Version 1 2 position2 External Maintenance Bypass Switch Version 2 3 position Cpnet Interface Card InstallationFunctions MOK Remote Emergency Power off 1 Connection of Remote EPO with N.C. contactDiesel Generator Operation Common Alarm Contacts Remote ResetInstallation of Hot-Standby Systems Installation Installation of the Interconnection Cable Installation of Parallel Systems Installation Installation Installation of the Interconnection Cables 11.3 Location of connectors on the IBYBP-CP pcbBattery Installation 12.1 Internal Battery connections Internal Electrical ConnectionsInstallation of External Batteries 12.3 B3/38 battery trays in the second and the third levelInstallation 12.6 B3/38 internal electrical connections 12.7 Battery cabinet B3/65 12.9 B3/65 internal electrical connections Connection Between UPS and Additional Battery Cabinets Connection of Auxiliary ContactsInitial Start-Up Start-Up ProcedureInitial START-UP ? Does this voltage have positive polarity? OK? Yes Static Switch Commutation CheckBattery Charging Current Limitation CheckAdditional Start-Up Proced. for Multi-Unit Systems Start-Up Procedure for Hot -standby Sys- temsAdditional START-UP PROCED. for MULTI-UNIT Systems Start-Up Procedure for Parallel Systems System START-UP has NOW Been Successfully Completed Sola 4000 Operation Chapters Operating Modes Operating ModesSola 4000 Operation GeneralLED Indication Operating Modes STAND-ALONE Unit Battery OperationOperating Modes Stand-alone Unit Normal OperationBypass Operation Maintenance Bypass OperationStandby Operation Operating Modes HOT-STANDBY Operation Operating Modes Hot-Standby OperationOperation with an Inverter Failure Operating Modes Hot-Standby Operation Operating Modes Parallel and Parallel/Redundant Operation Partial Load OperationOperating Modes Parallel and Parallel/Redundant Operation Operating Modes Parallel and Parallel/Redundant Operation Operating Instructions Switching On the UPS System / from Maintenance BypassInitial UPS Operating Mode Operating StepsFinal UPS Operating Mode Switching Off the UPS System / to Main- tenance Bypass CPHC16-SIPR IPRS1 ICPPB2 IRE IUG IRP Reset after Activating E.P.O Emergency Shut DownSola 4000 Operating Panel Chapters TablesSola 4000 Operating Panel Battery MonitoringFunctions Indication of Important DataUPS Operating Mode Indication Alarm signallingEmergency Power Off LED Indication LED IndicationLED 4 Battery Discharging LEDs Battery Indicator LED 28 E.P.OLED 30 Boost Charge Communication with a PC Communication with a PCConnection to PC Snmp Mode Service ModeAlarms Oscillator failure Static switch failure SSIStatic switch failure SSB IUG monitoring failureUPS status MeteringPanel Settings DIP Switch SettingsTAB 4.4 Setting of SW2 Location of DIP-switches and pushbuttons on the CPU/NCP pcb Installation Remote PanelFunctions UPS =1...8 identifies the UPSDIP-switch settings UPSx Followed bySola 4000 PCB Description Chapters UPS Control LogicSola 4000 PCB Description UPS Control LogicUPS Control Logic Rectifier IF/PS R Front ViewReset MAX. Vdc CPHC16 R Front ViewInverter Reset ICP Front ViewICT-2 Front View TP5IPS-500 Front View IPR front view Bypass IF/PS S Front View CPHC16 S Front View BypassSystem Data Sola 4000 Technical DataBattery Data Rectifier DataSola 4000 Technical Data System DataRectifier Data Battery Data Battery DataInverter Data Inverter Data