Powerware SOLA 4000 manual Inverter Data

Page 108

SOLA 4000 - Technical Data

4 Inverter Data

Technical Data / Inverter Data

 

 

 

 

Type SOLA 4000

 

 

 

 

 

 

 

 

 

 

 

 

 

10

 

15

20

30

40

60

80

100

120

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Permissible input DC voltage range

 

 

 

 

320 - 480 V/DC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Input power at rated load

 

 

 

 

 

 

 

 

 

 

-

[kW]

8,7

 

13

12,4

26

35,1

52,7

70,3

87,9

105,5

 

 

 

 

 

 

 

 

 

 

 

Inverter input current at 320 Vdc and rated

 

 

 

 

 

 

 

 

 

 

load

[A]

27

 

40

54

80

107,5

161,2

212,5

266

319

 

 

 

 

 

 

 

 

 

 

 

Nominal output current at rated load

 

 

 

 

 

 

 

 

 

 

(380V, cos phi = 0,8)

[A]

15,2

 

22,7

30,3

45,5

60,8

91,3

121,7

152,1

182,1

 

 

 

 

 

 

 

 

 

 

 

 

Nominal output current

(380V, cos phi = 1,0)

 

 

 

 

 

 

 

 

 

 

-

[A]

12,1

 

18,1

24,2

36,4

48,6

73

97,4

122

146

 

 

 

 

 

 

 

 

 

 

 

 

Efficiency at 80% load

 

 

 

 

 

 

 

 

 

 

 

-

[%]

> 92

 

> 92

> 92

> 92

> 92

> 93

> 93

> 93

> 93

 

 

 

 

 

 

 

 

 

 

 

Load power factor range

 

 

 

 

 

 

 

 

 

 

- at nominal load

 

0,7 - 0,8 ind.

 

 

 

 

 

 

 

- at reduced load

 

0,5 ind. - 0,5 cap.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output voltage

 

refer

to system data

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output voltage distortion (THD)

refer

to system data

 

 

 

 

 

 

 

 

 

 

 

Output voltage adjustment range

± 10% of programmable nominal value

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Phase displacement

 

 

 

 

 

 

 

 

 

 

 

- balanced load

 

120° ± 1%

 

 

 

 

 

 

 

- 100 % unbalanced load

120° ± 1%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Voltage tolerances

 

 

 

 

 

 

 

 

 

 

 

- static, balanced load

 

± 1 %

 

 

 

 

 

 

 

 

 

- static, 100% unbalanced load

± 1 %

 

 

 

 

 

 

 

 

 

- dynamic, 50% load step

± 4 %

 

 

 

 

 

 

 

 

 

- dynamic, 100% load step

± 5 %

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Voltage transient recovery time

<= 50 ms within ± 2% of nominal voltage

 

 

 

 

 

 

 

 

 

 

 

Short circuit current

 

150 % of nominal current

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Max. freq. range for synchr. of the inv. with

± 2,5 Hz

 

 

 

 

 

 

 

the mains

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Max. frequency variation during

± 1 Hz/sec.

 

 

 

 

 

 

 

synchronisation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FIG. 4.1 - Inverter Data

JUE 401269

108

Image 108
Contents Uninterruptible Power Supply Sola 4000 Operating Manual Safety Instructions Safety InstructionsSola 4000 Operating Manual Safety Instructions UPS Assembly Sola 4000 General System Description ChaptersUPS Assembly FeaturesSola 4000 General System Description Rectifier/Battery Charger UPS System StructureBattery Accumulator Static SwitchesInverter Under inverter failure conditions Maintenance Bypass Hot-Standby SystemsParallel-Redundant Systems Parallel SystemsEmergency Power Off Operating PanelFunctional Description Remote MonitoringSola 4000 Installation and Initial Start-Up ChaptersFigures InstallationAdditional START- UP Procedure for MULTI-UNIT SYSTEMS42 Initial START- UPSola 4000 Installation and Initial Start-Up Sola 4000 Installation and Initial Start-UpInstallation Mechanical InstallationWeight Floor Space RequiredRoom Size for 10-60 kVA UPS 6 UPS 10-60kVA room size JUERoom Size for 80-120 kVA UPS with auxiliary AC001 cabinet 7 UPS 80-120kVA room size JUERoom Size for 80-120 kVA UPS with auxiliary AC002 cabinet 8 UPS 80-120kVA room size JUEElectrical Installation General1 UPS connection diagram, version Input Cables / Fuses Mm²2 UPS connection diagram, version Output / Battery Cables Input CablesInput Fuses Installation of additional optional cabi- nets Sola 4000 with isolation transformer of the bypass supply3 UPS connection diagram, with THD filters Sola 4000 with THD filters4 Installation of 12-pulse units without galvanic isolation Sola 4000 with 12-pulse charger / rectifierInstallation of an External Maintenance Bypass 1 External Maintenance Bypass Switch Version 1 2 position2 External Maintenance Bypass Switch Version 2 3 position Installation Cpnet Interface CardFunctions MOK Remote Emergency Power off 1 Connection of Remote EPO with N.C. contactDiesel Generator Operation Common Alarm Contacts Remote ResetInstallation of Hot-Standby Systems Installation Installation of the Interconnection Cable Installation of Parallel Systems Installation Installation Installation of the Interconnection Cables 11.3 Location of connectors on the IBYBP-CP pcbBattery Installation 12.1 Internal Battery connections Internal Electrical ConnectionsInstallation of External Batteries 12.3 B3/38 battery trays in the second and the third levelInstallation 12.6 B3/38 internal electrical connections 12.7 Battery cabinet B3/65 12.9 B3/65 internal electrical connections Connection Between UPS and Additional Battery Cabinets Connection of Auxiliary ContactsStart-Up Procedure Initial Start-UpInitial START-UP ? Does this voltage have positive polarity? OK? Static Switch Commutation Check Battery Charging Current LimitationYes CheckStart-Up Procedure for Hot -standby Sys- tems Additional Start-Up Proced. for Multi-Unit SystemsAdditional START-UP PROCED. for MULTI-UNIT Systems Start-Up Procedure for Parallel Systems System START-UP has NOW Been Successfully Completed Sola 4000 Operation Chapters Operating Modes Sola 4000 OperationOperating Modes GeneralLED Indication Battery Operation Operating Modes Stand-alone UnitOperating Modes STAND-ALONE Unit Normal OperationMaintenance Bypass Operation Bypass OperationStandby Operation Operating Modes Hot-Standby Operation Operating Modes HOT-STANDBY OperationOperation with an Inverter Failure Operating Modes Hot-Standby Operation Operating Modes Parallel and Parallel/Redundant Operation Partial Load OperationOperating Modes Parallel and Parallel/Redundant Operation Operating Modes Parallel and Parallel/Redundant Operation Switching On the UPS System / from Maintenance Bypass Initial UPS Operating ModeOperating Instructions Operating StepsFinal UPS Operating Mode Switching Off the UPS System / to Main- tenance Bypass CPHC16-SIPR IPRS1 ICPPB2 IRE IUG IRP Reset after Activating E.P.O Emergency Shut DownSola 4000 Operating Panel Chapters TablesBattery Monitoring FunctionsSola 4000 Operating Panel Indication of Important DataUPS Operating Mode Indication Alarm signallingEmergency Power Off LED Indication LED IndicationLED 4 Battery Discharging LEDs Battery Indicator LED 28 E.P.OLED 30 Boost Charge Communication with a PC Communication with a PCConnection to PC Snmp Mode Service ModeAlarms Static switch failure SSI Static switch failure SSBOscillator failure IUG monitoring failureUPS status MeteringPanel Settings DIP Switch SettingsTAB 4.4 Setting of SW2 Location of DIP-switches and pushbuttons on the CPU/NCP pcb Installation Remote PanelFunctions UPS =1...8 identifies the UPSDIP-switch settings UPSx Followed bySola 4000 PCB Description Chapters UPS Control LogicUPS Control Logic Sola 4000 PCB DescriptionUPS Control Logic Rectifier IF/PS R Front ViewReset MAX. Vdc CPHC16 R Front ViewInverter Reset ICP Front ViewICT-2 Front View TP5IPS-500 Front View IPR front view Bypass IF/PS S Front View CPHC16 S Front View BypassSola 4000 Technical Data Battery DataSystem Data Rectifier DataSola 4000 Technical Data System DataRectifier Data Battery Data Battery DataInverter Data Inverter Data